Figure. 5.2.1. - 4. Example connection (S1 always to odd connector regardless the CT direction). CT direction is selected under
differential function
Please see the above gure, as a result of the direction of the CTs and according to the fact that P1/S1
side of the CTs are always wired to the odd inputs of the relay CT module, the “Differential calculation
mode” under the
Protection
→
TrafoModule
→
Idx> [87T,87N]
→
Settings
has to be set as “Subtract”.
Due to this the direction of measured currents are checked correctly from the relay perspective.
Initial data of the connection and the ratings are presented in following table.
AQ-T257
Instruction manual
Version: 2.00