Emissions
Conducted emissions
EN 60255-26 Ch. 5.2, CISPR 22
150kHz - 30 MHz
Radiated emissions
EN 60255-26 Ch. 5.1, CISPR 11
30 - 1 000 MHz
Immunity
Electrostatic discharge (ESD):
EN 60255-26, IEC 61000-4-2
Air discharge 15 kV
Contact discharge 8 kV
Fast transients (EFT):
EN 60255-26, IEC 61000-4-4
Power supply input 4kV, 5/50ns, 5kHz
Other inputs and outputs 4kV, 5/50ns, 5kHz
Surge:
EN 60255-26, IEC 61000-4-5
Between wires 2 kV / 1.2/50µs
Between wire and earth 4 kV / 1.2/50µs
Radiated RF electromagnetic eld:
EN 60255-26, IEC 61000-4-3
f = 80….1000 MHz 10V /m
Conducted RF eld:
EN 60255-26, IEC 61000-4-6
f = 150 kHz….80 MHz 10V
Table. 9.3. - 293. Voltage tests
Dielectric voltage test
EN 60255-27, IEC 60255-5, EN 60255-1
2 kV, 50Hz, 1min
Impulse voltage test
EN 60255-27, IEC 60255-5
5 kV, 1.2/50us, 0.5J
Physical environment compatibility
Table. 9.3. - 294. Mechanical tests
Vibration test
EN 60255-1, EN 60255-27, IEC 60255-21-1
2 ... 13.2 Hz ±3.5mm
13.2 ... 100Hz, ±1.0g
Shock and bump test
EN 60255-1,EN 60255-27, IEC 60255-21-2
20g, 1000 bumps/dir.
Table. 9.3. - 295. Environmental tests
Damp Heat
EN 60255-1, IEC 60068-2-30
Operational: 25-55°C, 97-93% Rh, 12+12h
Dry Heat
EN 60255-1, IEC 60068-2-2
Storage: 70°C, 16h
Operational: 55°C, 16h
Cold Test
EN 60255-1, IEC 60068-2-1
Storage: -40°C, 16h
Operational: -20°C, 16h
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
354