IL1FFT
Magnitudes (rms) of phase L1/A current components: Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
, harmonic 15
th
, harmonic 17
th
,
harmonic 19
th
harmonic current.
5 ms
IL2FFT
Magnitudes (rms) of phase L2/B current components: Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
, harmonic 15
th
, harmonic 17
th
,
harmonic 19
th
harmonic current.
5 ms
IL3FFT
Magnitudes (rms) of phase L3/C current components: Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
, harmonic 15
th
, harmonic 17
th
,
harmonic 19
th
harmonic current.
5 ms
I01FFT
Magnitudes (rms) of residual I01 current components: Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
, harmonic 15
th
, harmonic 17
th
,
harmonic 19
th
harmonic current.
5 ms
I02FFT
Magnitudes (rms) of residual I02 current components: Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
, harmonic 15
th
, harmonic 17
th
,
harmonic 19
th
harmonic current.
5 ms
Selection of the used AI channel and monitored harmonic as well as per unit monitoring or percentage
of fundamental monitoring is made with a setting parameter. In all possible input channel variations
pre-fault condition is presented with 20 ms averaged history value from -20 ms of Start or Trip event.
General settings
The function can be set to monitor the ratio of the measured harmonic to the measured fundamental
component or directly the per unit value of the harmonic current. Also the user needs to select the
correct measurement input.
Table. 5.4.6. - 82. Operating mode selection settings of the HOC function
Name
Range
Step
Default
Description
Ih> meas
side
De nes which current measurement module is
used by the function. Visible if unit has more than
one current measurement module.
1:
Side1
2:
Side2
-
1: Side1
Harmonic
selection
2
nd
harmonic
3
rd
harmonic
4
th
harmonic
5
th
harmonic
7
th
harmonic
9
th
harmonic
11
th
harmonic
13
th
harmonic
15
th
harmonic
17
th
harmonic
19
th
harmonic
-
2
nd
harmonic
Selection of the monitored
harmonic component
Per unit or
relative
x In
Ih/IL
-
x In
Selection of the monitored
harmonic mode. Either directly per
unit x In or in relation to the
fundamental frequency magnitude.
Measurement
input
IL1/IL2/IL3
I01
I02
-
IL1/IL2/IL3
Selection of the measurement input
either phase currents or residual
currents inputs.
Each HOC function instance provides these same settings. Multiple instances of HOC can be set to
operate independently of each other.
AQ-T257
Instruction manual
Version: 2.00
73
© Arcteq Relays Ltd