Figure. 5.5.1. - 100. Two of the voltage measurement connection options.
If the relay has full voltage connection with complete phase to phase or phase to ground voltages (left
side connection example 3LN+U4 (also 3LL + U4 and 2LL+U3+U4 modes) AVR measurement voltage
can be selected directly to U12, U23 or U31. In case only one voltage is available for AVR then it
should be connected to U4 input and the AVR needs to be set to measure from U4 channel and the
connected voltage (U12, U23 or U31).
General settings menu also includes on-line measurements and calculations from the AVR function as
well as the location of the tap changer. Information about the settings and AVR status is found in this
part.
Control settings
Control settings include the operating mode selection (Auto / Manual) and the control pulse length max
and minimum settings for the used output contacts. Instant operation the minimum wait time between
pulses is also set here.
Figure. 5.5.1. - 101. Control pulse timing settings.
AQ-T257
Instruction manual
Version: 2.00
207