General settings
General settings de ne the basic control voltage measurement con guration settings as well as give
overall information about AVR condition and status.
Table. 5.5.1. - 172. Measurement magnitudes used by the AVR function.
Signal
Description
Time base
U12 System
Phase to phase system voltage U12
5 ms
U23 System
Phase to phase system voltage U23
5 ms
U31 System
Phase to phase system voltage U31
5 ms
IL1
Phase current IL1
5 ms
IL2
Phase current IL2
5 ms
IL3
Phase current IL3
5 ms
General settings
General settings de ne the basic control voltage measurement con guration settings as well as give
overall information about AVR condition and status.
Table. 5.5.1. - 173. General settings parameters.
Name
Description
Range Step Default
Voltage measurement
Selection of the measured system voltage from
the U1, U2 and U3 inputs.
0: U12
1: U23
2: U31
3: U4
input
-
0:U12
U4 measure (visible only if Voltage
measurement is set to 3:U4 Input)
Selection of the measured system voltage from
the U4 input.
0: U12
1: U23
2: U31
-
0:U12
Table. 5.5.1. - 174. General settings indications and measurements.
Name
Description
Range
Step
Default
Avr settings
condition
(bitmask)
Internal information about settings. If the value differs from
0 settings are not correct.
1b: U>> set too
low
2b: U< set too
high
3b: U> set higher
than U>>
4b: U< set lower
than U<<
5b: U>>> set too
low
6b: U<<< set too
high
7b: VT selection
not ok
-
0
(settings
are ok)
AQ-T257
Instruction manual
Version: 2.00