DC 1…4
Input signal
select
0: 3PH.Fwd.Act.EP
1: 3PH.Rev.Avt.EP
2:
3PH.Fwd.React.EQ.CAP
3: 3PH.Fwd.React.EQ.IND
4:
3PH.Rev.React.EQ.CAP
5: 3PH.Rev.React.EQ.IND
-
0:
3PH.Fwd.Act.EP
Selects whether the energy is active or reactive,
whether the direction of the energy is forward of
reverse, and whether reactive energy is inductive or
capacitive.
DC 1…4
Input signal
-1 × 10
6
…1 × 10
6
0.01
-
The total amount of energy consumed.
DC 1…4
Pulse
magnitude
0…1800 kW/var
0.005
kW/var 1 kW/Var
The set pulse size. An energy pulse is given every
time the set magnitude is exceeded.
DC 1…4
Pulse length 0…1800 s
0.005
s
1 s
The total length of a control pulse.
DC1…4
Pulses sent
0…4 294 967 295
1
-
Indicates the total number of pulses sent.
Table. 5.2.3. - 37. DC 1…4 Pulse out settings
Name
Range
Step
Default
Description
DC 1…4 Pulse out
OUT1…OUTx
-
None selected
The selection of the controlled physical outputs.
Power measurements
The following power calculations are available when the voltage and the current cards are available.
Table. 5.2.3. - 38. Three-phase power calculations.
Name
Range
Step
Description
3PH Apparent
power (S)
-1x10
6
…
1x10
6
kVA
0.01
kVA
The total three-phase apparent power. In AQtivate, the row below
displays this in MVA.
3PH Active power
(P)
-1x10
6
…1x10
6
kW
0.01
kW
The total three-phase active power. In AQtivate, the row below displays
this in MW.
3PH Reactive power
(Q)
-1x10
6
…1x10
6
kVar
0.01
kVar
The total three-phase reactive power. In AQtivate, the row below displays
this in MVar.
3PH Tan(phi)
-1x10
6
…1x10
6
0.01
The direction of three-phase active power
3PH Cos(phi)
-1x10
6
…1x10
6
0.01
The direction of three-phase reactive power
Table. 5.2.3. - 39. Single phase power calculations (L1...L3).
Name
Range
Step
Description
Lx Apparent power (S)
-1x10
6
…1x10
6
kVA
0.01 kVA
The apparent power of Phase Lx
Lx Active power (P)
-1x10
6
…1x10
6
kW
0.01 kW
The active power of Phase Lx
Lx Reactive power (Q)
-1x10
6
…1x10
6
kVar
0.01 kVar
The reactive power of Phase Lx
Lx Tan(phi)
-1x10
6
…1x10
6
0.01
The direction of Phase Lx's active power
Lx Cos(phi)
-1x10
6
…1x10
6
0.01
The direction of Phase Lx's reactive power
Energy measurements
The following energy calculations are available when the voltage and the current cards are available.
Please note that the unit pre x is determined by the user's selection between 'kilo' and 'mega' in "Three-
phase energy pre x ("E 3ph M or k")" under the general "Power and energy measurement settings".
AQ-E215
Instruction manual
Version: 2.01
61