Additional
status
information
0: Open
Blocked
1: Open
Allowed
2: Close
Blocked
3: Close
Allowed
4: Object Ready
5: Object Not
Ready
6: Sync Ok
7: Sync Not Ok
-
-
Displays additional information about the status of the object.
Use
Synchrocheck
0: Not in use
1:
Synchrocheck
in use
-
0: Not
in use
Selects whether the "Synchrocheck" condition is in use for the circuit
breaker close command.
Use Object
ready
0: Ready High
1: Ready Low
2: Not in use
-
2: Not
in use
Selects whether the "Object ready" condition is in use for the circuit
breaker close command.
Open
requests
0…4 294 967
295
1
-
Displayes the number of successful "Open" requests.
Close
requests
0…4 294 967
295
1
-
Displays the number of successful "Close" requests.
Open
requests
failed
0…4 294 967
295
1
-
Displays the number of failed "Open" requests.
Close
requests
failed
0…4 294 967
295
1
-
Displays the number of failed "Close" requests.
Clear
statistics
0: -
1: Clear
-
0: -
Clears the request statistics, setting them back to zero (0).
Automatically returns to "-" after the clearing is nished.
Table. 5.5.2. - 83. Object types.
Name
Functionalities
Description
Withdrawable circuit breaker
WD cart position
Position
Control
Object ready
Use synchrocheck
Interlocks
The monitor and control con guration of the withdrawable circuit breaker.
Circuit breaker
Position indication
Control
Object ready
Use synchrocheck
Interlocks
The monitor and control con guration of the circuit breaker.
Disconnector (MC)
Position indication
Control
The position monitoring and control of the disconnector.
Disconnector (GND)
Position indication
The position indication of the earth switch.
Table. 5.5.2. - 84. I/O.
Signal
Range
Description
Objectx Open input
("Objectx Open Status
In")
Digital
input or
other
logical
signal
selected
by the user
(SWx)
A link to a physical digital input. The monitored object's OPEN status. "1" refers to
the active open state of the monitored object. Position indication of digital inputs and
protection stage signals can be done by using IEC 61850 signals, GOOSE signals or
logical signals.
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
102