IL1
Polarity
0: -
1: Invert -
0: -
The selection of the rst current measurement channel's (IL1) polarity (direction).
The default setting is for the positive current to flow from connector 1 to connector
2, with the secondary currents' starpoint pointing towards the line.
IL2
Polarity
0: -
1: Invert -
0: -
The selection of the second current measurement channel's (IL2) polarity
(direction). The default setting is for the positive current to flow from connector 3 to
connector 4, with the secondary currents' starpoint pointing towards the line.
IL3
Polarity
0: -
1: Invert -
0: -
The selection of the third current measurement channel's (IL3) polarity (direction).
The default setting is for the positive current to flow from connector 5 to connector
6, with the secondary currents' starpoint pointing towards the line.
CT
scaling
factor P/S
-
-
-
A relay feedback value; the calculated scaling factor that is the ratio between the
primary current and the secondary current.
CT
scaling
factor
NOM
-
-
-
A relay feedback value; the calculated scaling factor that is the ratio between the
set primary current and the set nominal current.
Ipu
scaling
primary
-
-
-
A relay feedback value; the scaling factor for the primary current's per-unit value.
Ipu
scaling
secondary
-
-
-
A relay feedback value; the scaling factor for the secondary current's per-
unit value.
Table. 5.2.1. - 8. Settings of the Residual I01 CT scaling.
Name
Range
Step Default
Description
I01 CT
primary
0.2…25
000.000 A
0.000
01 A
100.0 A The rated primary current of the current transformer.
I01 CT
secondary
0.1…
10.000 A
0.000
01 A
5.0 A
The rated secondary current of the current transformer.
I01
Polarity
0: -
1: Invert
-
0: -
The selection of the coarse residual measurement channel's (I01) polarity
(direction). The default setting is for the positive current to flow from connector
7 to connector 8.
CT
scaling
factor P/S
-
-
-
A relay feedback value; the calculated scaling factor that is the ratio between the
primary current and the secondary current.
Table. 5.2.1. - 9. Settings of the Residual I02 CT scaling.
Name
Range Step Default
Description
I02 CT
primary
0.2…25
000.0 A
0.000
01 A
100.0 A The rated primary current of the current transformer.
I02 CT
secondary
0.001…
10.0A
0.000
01 A
5.0 A
The rated secondary current of the current transformer.
I02
Polarity
0: -
1: Invert -
0: -
The selection of the sensitive residual measurement channel's (I02) polarity
(direction). The default setting is for the positive current to flow from connector 9 to
connector 10.
CT
scaling
factor P/S
-
-
-
A relay feedback value; the calculated scaling factor that is the ratio between the
primary current and the secondary current.
Measurements
The following measurements are available in the measured current channels.
Table. 5.2.1. - 10. Per-unit phase current measurements.
Name
Range
Step
Description
AQ-E215
Instruction manual
Version: 2.01
43