Table. 6.1.3. - 122. Module settings.
Name
Range
Description
I/O module X
address
0…247
De nes the Modbus unit address for the selected I/O Module (A, B, or C). If this setting
is set to "0", the selected module is not in use.
Module x
type
0: ADAM-4018+
1: ADAM-4015
Selects the module type.
Channels in
use
Channel 0…
Channel 7 (or None)
Selects the number of channels to be used by the module.
Table. 6.1.3. - 123. Channel settings.
Name
Range
Step Default
Description
T.C.
type
0: +/- 20
mA
1: 4…20
mA
2: Type J
3: Type K
4: Type T
5: Type E
6: Type R
7: Type S
-
1: 4…
20 mA
Selects the thermocouple or the mA input connected to the I/O module.
Types J, K, T and E are nickel-alloy thermocouples, while Types R and S are
platinum/rhodium-alloy thermocouples.
Input
value
-101.0…2
000.0
0.1
-
Displays the input value of the selected channel.
Input
status
0: Invalid
1: OK
-
-
Displays the input status of the selected channel.
6.1.4. IEC 61850
The user can enable the IEC 61850 protocol in device models that support this protocol. The AQ-200
series devices use Edition 1 of IEC 61850. The following services are supported by IEC 61850 in
Arcteq devices:
Dataset (prede ned data sets can be edited with the IEC 61850 tool in AQtivate)
Report Control Blocks (both buffered and unbuffered reporting)
Control ('direct operate with normal security’ control sequences)
Disturbance recording le transfer
GOOSE
Time synchronization
The device's current IEC 61850 setup can be viewed with the IEC61850 tool (
Tools
→
IEC 61850
). By
browsing the 61850 tree one can see the full list of available logical nodes in the Arcteq
implementation.
AQ-E215
Instruction manual