Primary calculated I0
("Pri.calc.I0")
0.00…1 000
000.0 A
0.01
A
The primary fundamental frequency RMS current measurement from the
calculated current channel I0.
Primary residual
current I0x TRMS
("Res.curr.I0x TRMS
Pri")
0.00…1 000
000.0 A
0.01
A
The TRMS current (inc. harmonics up to 31
st
) measurement from the
primary residual current channel I01 or I02.
Table. 5.2.1. - 16. Secondary residual current measurements.
Name
Range Step
Description
Secondary residual
current I0x
("Sec.Res.curr.I0x")
0.00…
300.0 A
0.01
A
The secondary fundamental frequency RMS current measurement from the
residual current channel I01 or I02.
Secondary calculated
I0
("Sec.calc.I0")
0.00…
300.0 A
0.01
A
The secondary fundamental frequency RMS current measurement from the
calculated current channel I0.
Secondary residual
current I0x TRMS
(Res.curr.I0x TRMS
Sec")
0.00…
300.0 A
0.01
A
The secondary TRMS current (inc. harmonics up to 31
st
) measurement from the
secondary residual current channel I01 or I02.
Table. 5.2.1. - 17. Residual phase angle measurements.
Name
Range
Step
Description
Residual current angle
I0x
("Res.curr.angle I0x")
0.00…360.00
deg
0.01
deg
The residual current angle measurement from the I01 or I02 current
input.
Calculated I0 phase
angle
("calc.I0 Pha.angle")
0.00…360.00
deg
0.01
deg
The calculated residual current angle measurement.
Table. 5.2.1. - 18. Per-unit sequence current measurements.
Name
Range
Step
Description
Positive sequence
current
("Pos.seq.curr.")
0.00…1250.0 ×
In
0.01 ×
In
The measurement (in p.u.) from the calculated positive sequence
current.
Negative sequence
current
("Neg.seq.curr.")
0.00…1250.0 ×
In
0.01 ×
In
The measurement (in p.u.) from the calculated negative sequence
current.
Zero sequence current
("Zero seq.curr.")
0.00…1250.0 ×
In
0.01 ×
In
The measurement (in p.u.) from the calculated zero sequence
current.
Table. 5.2.1. - 19. Primary sequence current measurements.
Name
Range
Step
Description
Primary positive sequence
current
("Pri.Pos.seq.curr.")
0.00…1 000
000.0 A
0.01
A
The primary measurement from the calculated positive
sequence current.
Primary negative sequence
current
("Pri.Neg.seq.curr.")
0.00…1 000
000.0 A
0.01
A
The primary measurement from the calculated negative
sequence current.
Primary zero sequence
current
("Pri.Zero seq.curr.")
0.00…1 000
000.0 A
0.01
A
The primary measurement from the calculated zero sequence
current.
Table. 5.2.1. - 20. Secondary sequence current measurements.
Name
Range
Step
Description