Figure. 5.5.4. - 70. Activating mA output channels.
Table. 5.5.4. - 92. Main settings (output channels).
Name
Range
Default
Description
mA option
card 1
Enable mA output channels 1
and 2
0:
Disabled
1: Enabled
0:
Disabled
Enables and disables the outputs of the mA
output card 1.
Enable mA output channels 3
and 4
mA option
card 2
Enable mA output channels 5
and 6
0:
Disabled
1: Enabled
0:
Disabled
Enables and disables the outputs of the mA
output card 2.
Enable mA output channels 7
and 8
Table. 5.5.4. - 93. Settings for mA output channels.
Name
Range
Step
Default
Description
Enable mA
output
channel
0: Disabled
1: Enabled
-
0: Disabled
Enables and disables the selected mA output channel. If the
channel is disabled, the channel settings are hidden.
Magnitude
selection for
mA output
channel
0: Currents
1: Voltages
2: Powers
3: Impedance
and admittance
4: Other
-
0: Currents
De nes the measurement category that is used for mA
output control.
Magnitude of
mA output
channel
(dependent on
the measurement
category
selection)
-
(dependent on
the
measurement
category
selection)
De nes the measurement magnitude used for mA output
control. The available measurements depend on the
selection of the "Magnitude selection for mA output channel"
parameter.
Input value 1
-10
7
…10
7
0.001
0
The rst input point in the mA output control curve.
Scaled mA
output value
1
0.0000…
24.0000 mA
0.0001
mA
0 mA
The mA output value when the measured value is equal to or
less than Input value 1.
Input value 2
-10
7
…10
7
0.001
1
The second input point in the mA output control curve.
Scaled mA
output value
2
0.0000…
24.0000 mA
0.0001
mA
0 mA
The mA output value when the measured value is equal to or
greater than Input value 2.
AQ-E215
Instruction manual
Version: 2.01
115
© Arcteq Relays Ltd