27
IMPLEMENT SETTINGS
11.9.2
Tank level zero value
If the VT detects the presence of fluid inside tank, even if empty, set the level sensor to zero;
To use this menu the level sensor must be active (Tank level source,
chap
).
PERFORM THE ADJUSTMENT WITH EMPTY TANK.
1
Start the procedure by pressing
Start
.
2
Press
Confirmation
to reset the level sensor residual signal.
1
Fig. 52
2
Value too low!
Value too high!
Unstable signal!
If this alarm is displayed, faulty values have been detected: check the
conditions described at the beginning of the paragraph (no residual fluid,
level sensor active). If the problem persists, check the correct connection and
operation of sensor.
Quits without confirming the
changes
Saves the changes
Delete
Quit
Confirm
Goes back to previous menu,
or scrolls the pages of a menu
(previous page)
Scrolls the pages of a menu
(next page)
Goes back to Main screen
Saves the changes to current
page