FST 500 Manual
- Page 98 -
Pr.103 Auto Tune Motor parameters
Factory Setting: 00
Settings
00 Disable
01 Auto tune for R1
02 Auto tune for R1 + No Load testing
★
For Auto Tune, set Pr.103 to 01 or 02 and press the RUN key. When it is set to 02, motor should
have no load.
Pr.104 R1 Value
Settings 00 to 65535Mω Factory Setting: 00
★
As an option to Auto Tune, this parameter inputs the motor resistance.
Pr.105 Control Mode
Factory Setting: 00
Settings
00 V/F Control
01 Sensor-less Control
Pr.106 Rated Slip Unit: 0.01Hz
Settings 0.00 to 10.00 Hz Factory Setting: 3.0
◆
Example of Slip calculation: The rated sp
eed of 4 poles/3 φ/ 60Hz/ 220V on the nameplate is
1710RPM. The rated slip is then: 60-(1710/(120/P))=3Hz. (being P the number of poles)
Pr.107 Vector Voltage Filter Unit: 2ms
Settings 5 to 9999 Factory Setting: 10
Pr.108 Vector Slip Compensation Filter Unit: 2ms
Settings 25 to 9999 Factory Setting: 50
★
This parameter sets the low-pass filter in vector control.
★
Example: Pr. 107 = 10 X 2ms =20ms, Pr. 108 = 50 X 2 ms =100ms.
Pr.109 Selection for Zero Speed Control
Factory Setting: 00
Summary of Contents for FST-500 Series
Page 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Page 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Page 17: ...FST 500 Manual Page 17...
Page 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Page 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Page 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Page 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Page 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Page 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Page 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Page 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Page 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Page 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Page 134: ...FST 500 Manual Page 134...
Page 135: ...FST 500 Manual Page 135...
Page 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...