FST 500 Manual
- Page 75 -
Pr.67 Skip Frequency 1 Unit: 0.1 Hz
Pr.68 Skip Frequency 2 Unit: 0.1 Hz
Pr.69 Skip Frequency 3 Unit: 0.1 Hz
Settings 0.00 to 400.0 Hz Factory Setting: 0.00
★
These three parameters determine the three Skip Frequencies that in conjunction with Pr.70, Skip
Frequency Band, will cause the AC drive to skip operating in each frequency band. Note: Pr.67 >
Pr.68 > Pr.69.
Pr.70 Skip Frequency Band Unit: 0.1 Hz
Settings 0.00 to 20.00 Hz Factory Setting: 0.00
★
This parameter determines the frequency band for a given Skip Frequency. Half of the Skip
Frequency Band is above the Skip Frequency and the other half is below. Programming this
parameter to 0.1 disables all skip frequencies.
Pr.71 PWM Carrier Frequency
Settings 115V series
230V series 01 to 15 (1KHz to 15KHz) Factory Setting: 15
460V series FST-500-7R5T4 is 10
. 575V series 01 to 10 (1KHz to 10KHz) Factory Setting: 6
Note: 1-9kHz in sensorless vector control mode
★
The parameter defines the carrier frequency of the PWM (Pulse-Width Modulated) output.
Summary of Contents for FST-500 Series
Page 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Page 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Page 17: ...FST 500 Manual Page 17...
Page 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Page 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Page 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Page 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Page 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Page 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Page 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Page 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Page 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Page 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Page 134: ...FST 500 Manual Page 134...
Page 135: ...FST 500 Manual Page 135...
Page 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...