FST 500 Manual
- Page 34 -
Parameter
Explanation
Settings
Factory
Setting
Pr.30
DC Braking during
Stopping
0.0 to 25.0 sec
0.0
Pr.31
Start-point for DC
Braking
0.00 to 60.00 Hz
0.00
Pr.32
Momentary Power
Loss Operation
Selection
00: Stop operation after momentary power loss
01: Continues after momentary power loss, speed
search starts with Master Frequency
02: Continues after momentary power loss,
speed search starts with Minimum output
Frequency
00
Pr.33
Maximum Allowable
Power Loss Time
0.3 to 5.0 sec
2.0
Pr.34
Base-Block Time for
Speed Search
0.3 to 5.0 sec
0.5
Pr.35
Maximum Current
Level for Speed
Search
30 to 200 %
150
Pr.36
Upper Bound of
Output Frequency
0.10 Hz to 400.0 Hz
400.0
Pr.37
Lower Bound of
Output Frequency
0.00 Hz to 400.0 Hz
0.00
Pr.38
Multi-function Input
Terminal (M0,M1)
00: M0: FWD/STOP, M1: REV/STOP
01: M0: RUN/STOP, M1: REV/FWD
02: M0, M1, M2: 3-wire operation control mode
00
Pr.39
Multi-function Input
Terminal (M2)
00: No Function
01: Output OFF (N.O.) (enabled when running)
02: Output OFF (N.C.) (enabled when running)
03: External Fault (normally open) N.O.
04: External Fault (normally close) N.C
05: RESET
06: Multi-Step Speed Command 1
07: Multi-Step Speed Command 2
08: Multi-Step Speed Command 3
09: Jog Operation
10: Accel/Decel Speed Inhibit
11: First or Second Accel/Decel Time
12: Base-block (B.B.) (N.O)
13: Base-block (B.B.) (N.C)
14: Increase Master Frequency
15: Decrease Master Frequency
16: Run PLC Program
17: Pause PLC
18: Counter Trigger Signal
19: Counter Reset
20: No function
21: RESET command (N.C)
22: Control source: External Terminal
23: Control source: Keypad
24: Control source: Communication
25: Parameter Lock (Write disable, Read is always 0)
26: PID Disable (N.O.)
27: PID Disable (N.C.)
28: Second Source for Frequency Command
29: Forward (contact is open) / Reverse
(contact is close)
05
Pr.40
Multi-function Input
Terminal (M3)
06
Pr.41
Multi-function Input
Terminal (M4)
07
Pr.42
Multi-function Input
Terminal (M5)
08
Summary of Contents for FST-500 Series
Page 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Page 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Page 17: ...FST 500 Manual Page 17...
Page 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Page 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Page 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Page 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Page 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Page 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Page 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Page 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Page 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Page 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Page 134: ...FST 500 Manual Page 134...
Page 135: ...FST 500 Manual Page 135...
Page 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...