FST 500 Manual
- Page 73 -
Pr.60 Over-Torque Detection Mode
Factory Setting: 00
Settings: 00 Over-Torque detection disabled.
01 Enabled during constant speed operation until the allowable time for detection
(Pr.62) elapses.
02 Enabled during constant speed operation and halted after detection.
03 Enabled during acceleration until the allowable time for detection (Pr.62) elapses.
04 Enabled during acceleration and halted after detection.
Pr.61 Over-Torque Detection Level Unit: 1%
Settings 30 to 200% Factory Setting: 150
●
A setting of 100% is proportional to the Rated Output Current of the drive.
●
This parameter sets the Over-Torque Detection level in 1% increments. (The AC drive rated
current is equal to 100%.)
Pr.62 Over-Torque Detection Time Unit: 0.1 sec
Settings 0.0 to 10.0sec Factory Setting: 0.1sec
◆
This is the duration for over-torque detection. When the output current is larger than the
over-torque detection level (Pr.61), an over-torque condition exists and the detection time (Pr.62) is
timed-out. Any of the multi-function output terminals set to indicate over-torque, will then close.
(Please refer to Pr. 45 and Pr.46)
Pr.63 Loss of ACI (4-20mA)
Factory Setting: 00
Settings: 00 Decelerate to 0 Hz
01 Stop immediately and display "EF"
02 Continue operation by last frequency command
Pr.64 User Defined Function for Display
Factory Setting: 06
Settings: 00 Displays AC drive output frequency (Hz)
01 Display User-defined output Frequency (H*Pr.65)
02 Output Voltage (E)
03 DC Bus Voltage (u)
04 PV (i)
05 Displays the value of the internal counter (c)
06 Displays the setting Frequency (F)
07 Displays the parameter setting (P)
Summary of Contents for FST-500 Series
Page 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Page 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Page 17: ...FST 500 Manual Page 17...
Page 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Page 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Page 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Page 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Page 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Page 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Page 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Page 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Page 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Page 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Page 134: ...FST 500 Manual Page 134...
Page 135: ...FST 500 Manual Page 135...
Page 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...