FST 500 Manual
- Page 19 -
2.3 Main Circuit
2.3.1 Main Circuit Connection
******************************************************************************************************************
!
Mains power terminals (R/L1, S/L2, T/L3)
Connect these terminals (R/L1, S/L2, T/L3) via a non-fuse breaker or earth leakage breaker to
3-phase AC power (some models to 1-phase AC power) for circuit protection. It is unnecessary to
consider phase-sequence.
It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off power
quickly and reduce malfunction when activating the protection function of AC motor drives. Both
ends of the MC should have an R-C surge absorber.
Please make sure to fasten the screw of the main circuit terminals to prevent sparks which is
made by the loose screws due to vibration.
Please use voltage and current within the regulation shown in Appendix A.
When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of
200mA, and not less than 0.1-second detection time to avoid nuisance tripping.
Do NOT run/stop AC motor drives by turning the power ON/OFF. Run/stop AC motor drives by
RUN/STOP command via control terminals or keypad. If you still need to run/stop AC drives by
turning power ON/OFF, it is recommended to do so only ONCE per hour.
Do NOT connect 3-phase models to a 1-phase power source.
Terminal Symbol
Explanation of Terminal Function
R/L1, S/L2, T/L3
AC line input terminals (three phase)
U/T1, V/T2, W/T3
Motor connections
B1
– B2
Connections for brake resistor (optional)
Earth Ground
Summary of Contents for FST-500 Series
Page 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Page 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Page 17: ...FST 500 Manual Page 17...
Page 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Page 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Page 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Page 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Page 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Page 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Page 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Page 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Page 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Page 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Page 134: ...FST 500 Manual Page 134...
Page 135: ...FST 500 Manual Page 135...
Page 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...