Pr. 126 PID Offset Level
Settings 1.0 to 50.0 % Factory Setting: 10.0
◆
This parameter is used to set the offset between set point and feedback.
Pr. 127 Detection Time of PID Offset
Settings 0.1 to 300.0 sec Factory Setting: 5.0
★
This parameter is used to set the detection time of PID offset.
Pr. 128 Minimum Reference Value Unit: 0.1V
Settings 0.0 to 10.0 V Factory Setting: 0.0
●
This parameter is used to set the AVI input voltage that corresponds to minimum frequency.
Pr. 129 Maximum Reference Value
Settings 0.0 to 10.0 V Factory Setting: 10.0
★
This parameter is used to set the AVI input voltage that corresponds to maximum frequency.
Pr. 130 Invert Reference Signal AVI (0-10V)
Factory Setting: 00
Settings
00 Not Inverted
01 Inverted
★
If this parameter is set to 01, the reference signal is inverted: 0V corresponds to 60Hz in Pr.128
and 10V corresponds to 0Hz in Pr.129.
Pr. 131 Minimum Reference Value (0-20mA) Unit: 0.1mA
Settings 0.0 to 20.0mA Factory Setting: 4.0
◆
This parameter is used to set the ACI input frequency that corresponds to minimum frequency.
Pr. 132 Maximum Reference Value (0-20mA) Unit: 0.1mA
Settings 0.0 to 20.0mA Factory Setting: 20.0
Summary of Contents for FST-500 Series
Page 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Page 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Page 17: ...FST 500 Manual Page 17...
Page 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Page 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Page 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Page 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Page 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Page 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Page 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Page 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Page 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Page 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Page 134: ...FST 500 Manual Page 134...
Page 135: ...FST 500 Manual Page 135...
Page 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...