Pr.33 Maximum Allowable Power Loss Time Unit: 0.1sec
Settings 0.3 to 5.0 sec Factory Setting: 2.0 sec
★
After a power loss, the AC drive will resume operation only if the power loss duration is shorter
than the time defined by Pr.33. If the Maximum Allowable Power Loss Time is exceeded, the AC
drive output is then turned off.
Pr.34 Base-Block Time for Speed Search Unit: 0.1sec
Settings 0.3 to 5.0 sec Factory Setting: 0.5 sec
★
When a momentary power loss is detected, the AC drive will stop its output and will wait during a
specified time interval called Base Block (entered in Pr.34) before resuming operation. Setting of
this parameter should make the residual output voltage due to regeneration almost
zero, before the drive resumes operation.
★
This parameter also determines the search time when performing external Base-Block and Fault
Reset (Pr.72).
Pr.35 Maximum Current Level for Speed Search Unit: 1%
Settings 30 to 200% Factory Setting: 150
★
Following a power failure, the AC drive will start its speed search operation only if the output
current is greater than the value determined by Pr.35. When the output current is less than that of
Pr.35, the AC d
rive output frequency is at a “speed synchronization point” and will accelerate or
decelerate back to the operating frequency at which it was running prior to the power failure.
Summary of Contents for FST-500 Series
Page 8: ...FST 500 Manual Page 8 1 1 3 External Parts and Labels...
Page 9: ...FST 500 Manual Page 9 1 1 4 Remove instructions...
Page 17: ...FST 500 Manual Page 17...
Page 22: ...FST 500 Manual Page 22 2 4 Control Terminal Wiring Factory Settings...
Page 27: ...FST 500 Manual Page 27 3 1 2 How to Operate the Digital Keypad LC M02E...
Page 49: ...FST 500 Manual Page 49 Commonly used V F Setting 1 General Purpose...
Page 110: ...FST 500 Manual Page 110 Chapter 5 Troubleshooting 5 1 Over Current OC...
Page 111: ...FST 500 Manual Page 111 5 2 Ground Fault 5 3 Over Voltage OV...
Page 112: ...FST 500 Manual Page 112 5 4 Low Voltage Lv...
Page 113: ...FST 500 Manual Page 113 5 5 Over Heat OH1 5 6 Overload...
Page 114: ...FST 500 Manual Page 114 5 7 Keypad Display is Abnormal 5 8 Phase Loss PHL...
Page 115: ...FST 500 Manual Page 115 5 9 Motor cannot Run...
Page 116: ...FST 500 Manual Page 116 5 10 Motor Speed cannot be Changed...
Page 134: ...FST 500 Manual Page 134...
Page 135: ...FST 500 Manual Page 135...
Page 145: ...FST 500 Manual Page 145 EMI Filter 40TDS4W4B Used on 5 7 5 HP 230V Three Phase Models...