7. The factory setting for
“
Channel One Function” is magnet 1
position. For most all applications this setting is not typically
changed. For sensors ordered with 2 output channels, the
“
Channel Two Function” setting can be used for the other
available output functions. These are:
magnet 2 position, magnet 1 speed, magnet 1 velocity, magnet
1 reverse position, temperature inside the sensor electronics
housing, and the differential between magnet 1 and 2.
For this example with 1 output channel, the next setting can be
used to adjust the magnet 1 positions for set point one (start of
stroke) and set point two (end of stroke). Click on “Read Magnet”
to retrieve the currently measured position value for magnet 1.
Confirm your changes by clicking the SUBMIT button.
Fig. 74: Adjusting magnet 1 set point positions
8. The channel one over range setting allows the position output
values to continue to increase or decrease when the magnet
travels beyond the active stroke range. In some instances,
controllers that were programmed to expect the position values
to continue changing, even when the magnet travels into the
null or dead zone areas, can trigger a controller error condition
when using the R-Series
V
Analog sensor, unless this over range
setting is enabled. Confirm your changes by clicking the SUBMIT
button.
Fig. 75: Enabling the
“
Channel One Over Range
”
setting