3. The sensor shown in this example has been configured in the
factory for an output range of 4
…
20 mA. By clicking the pencil
to the right of “Configurable Range” the pencil changes to red
and a drop-down box is opened to allow adjusting the values.
For this example, the output range is changed to 0…20 mA. You
can change the values via the drop-down menu. Confirm your
changes by clicking the SUBMIT button.
Fig. 70: Adjusting the sensor’s output range
4. The next setting is for output at set point one (start of stroke).
For this example, the new value is 0.1 mA, as shown in the drop-
down box. Confirm your changes by clicking the SUBMIT button.
Fig. 71: Adjusting the output value for set point one