background image

En-5

4. PIPE INSTALLATION

 CAUTION

Be careful that foreign matter (oil, water, etc.) does not enter the piping with refrigerant 
R410A models. Also, when storing the piping, securely seal the openings by pinching, 
taping, etc.

While brazing the pipes, be sure to purge with dry nitrogen gas.

4.1. Selecting the pipe material

 CAUTION

Do not use existing pipes.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil or water.

It is necessary to use seamless copper pipes.
Material: Phosphor deoxidized seamless copper pipes.
It is desirable that the amount of residual oil is less than 40 mg/10 m.

Do not use copper pipes that have a collapsed, deformed, or discolored portion (es-
pecially on the interior surface). Otherwise, the expansion valve or capillary tube may 
become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional refrigerant, it is necessary to 
choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown in the table.

• 

Never use copper pipes thinner than those indicated in the table even if they are available 

• 

on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [mm (in.)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

4.2. Pipe requirement

 CAUTION

Refer to the Installation Manual of the outdoor unit for description of the length and the 
diameter of connecting pipe or for difference of its elevation.

Use pipe with water-resistant heat insulation.

• 

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause 
water leaks. 
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only) 
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70%, install heat insulation around the refrigerant piping. If the 
expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if 
the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker. If 
heat insulation is used that is not as thick as specifi ed, condensation may form on the 
surface of the insulation. 
In addition, use heat insulation with heat conductivity of 0.045W/(m·K) or less (at 20 °C).

4.3. Flare connection (pipe connection)

4.3.1. Flaring

Use special pipe cutter and fl are tool exclusive for R410A.

• 
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert the fl are nut (always use the fl are nut attached to the indoor and outdoor units 

respectively) onto the pipe and perform the fl are processing with a fl are tool. Leakage 
of refrigerant may result if other fl are nuts are used.

(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

B

A

L

Check if [L] is fl ared uniformly 
and is not cracked or scratched.

Die

Pipe

Pipe outside diameter 

[mm (in.)]

Dimension A [mm]

Dimension B

-

0
0.4 

[mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional fl are tools to fl are R410A pipes, the dimension A should be ap-
proximately 0.5 mm more than indicated in the table (for fl aring with R410A fl are tools) to 
achieve the specifi ed fl aring. Use a thickness gauge to measure the dimension A.

Width across 

fl ats

Pipe outside diameter 

[mm (in.)]

Width across fl ats of 

Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

4.3.2 Bending pipes

If pipes are shaped by hand, be careful not to collapse them.

• 

Do not bend the pipes at an angle more than 90°.

• 

When pipes are repeatedly bend or stretched, the material will harden, making it diffi cult 

• 

to bend or stretch them any more. 
Do not bend or stretch the pipes more than 3 times.

• 

 CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection

 CAUTION

Be sure to connect the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the fl are nut cannot tightened smoothly. If the fl are nut 
is forced to turn, the threads will be damaged.

Do not remove the fl are nut from the indoor unit pipe until immediately before connecting 
the connection pipe.

Do not use mineral oil on fl ared part. Prevent mineral oil from getting into the system as 
this would reduce the lifetime of the units.

(1) Detach the caps and plugs from the pipes.
(2) Center the pipe against the port on the indoor unit, and then turn the fl are nut by hand.

Connection pipe 
(Gas)

Connection pipe 
(Liquid)

Indoor unit

(3) When the fl are nut is tightened properly by your hand, hold the body side coupling with 

a separate spanner, then tighten with a torque wrench. (See the table below for the 
fl are nut tightening torques.

9379124010-05_IM.indb   5

9379124010-05_IM.indb   5

8/31/2012   10:43:20 AM

8/31/2012   10:43:20 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for AUYG14LVLB

Page 1: ...βις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Cassette Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ü T й и к с с у Р PART NO 9379124010 05 9379124010 ...

Page 2: ...eration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area Touching the refrigerant directly can c...

Page 3: ...ssette grille Hook wire 2 For suspending the Cassette grille Screw pitch small M4 10 mm 2 For mounting the Hook Wire for metals Screw pitch large M4 10 mm 4 For mounting the L angle and Hook wire for resins 2 5 Optional parts Parts name Model No Summary Wired remote controller UTY RNN M Unit control is performed by wired remote controller Simple Remote Controller UTY RSN M For air conditioner oper...

Page 4: ...ong and durable ceiling 262 or more 1 000 or more 1 800 or more 1 000 or more Unit mm Floor Obstruction This product can be installed at a height of up to 3 000mm However 7000 9000 Btu h model can not be installed in high places Perform the Function Setting on the remote control in accordance with the installed height See 8 2 Function setting Discharge direction setting The discharge direction can...

Page 5: ...p Air bleeding When lifting up drain Height of inclined pipe should be less than 700 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 mm or less from the unit 300 mm or less VP25 O D 32 mm local arrangement 700 mm or less Horizontal or upward gradient Downward gradient 1 100 to 1 50 VP30 O D 38 mm or more Downward gradient 1...

Page 6: ...flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other fla...

Page 7: ...nnections Improp erly connected or secured wires can cause serious accidents such as overheating the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with ...

Page 8: ...R UNIT R W B Red White Black Wired remote controller cable Indoor unit Remote controller cable Earth Ground the remote controller if it has a earth ground line Wired remote controller R W B Simultaneous twin 18 22 24 type only Connection cable Indoor unit Primary Indoor unit Secondary Junction box Lo cal purchase Outdoor unit Earth Ground line Control line Power line Earth Ground line Wired remote...

Page 9: ...ires Power supply cable or connection cable 20 mm 40mm or more Earth ground wire Use a 4 core wire cable 5 3 Connection of wiring 1 Remove the control box cover and install each connection wire Screw Control box cover 2 After wiring is complete secure the remote controller cable and transmission cable with the attached the cable tie and the clamper Detail a a Wire clamper accessory Bind securely T...

Page 10: ... Select a place that will not be affected by the heat from a stove etc Install the remote controller with a distance of 7 m between the remote controller and the photocell as the criteria However when installing the remote controller check that it operates positively Install the remote controller holder to a wall pillar etc with the tapping screw Mount the holder 1 Screws Set the remote controller...

Page 11: ...through the normal process refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE 1 Press the SET TEMP button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 2 Press the TIMER MODE button and check that the indoor unit can receive signals at ...

Page 12: ...or or remote controller unit sensor 8 Wireless remote controller signal code Change the indoor unit Signal Code depending on the wireless remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 9 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operati...

Page 13: ...supply cable Bus wire Remote controller cable Indoor unit 1 primary Indoor unit 2 secondary Indoor unit 3 secondary Set the R C address DIP switc h setting 2 Set the R C address of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set to make the R C address 00 Indoor unit R C address DIP SWITCH No 1 2 3 4 1 00...

Page 14: ...roller setting 4 Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 After completing the function settings turn off all of the indoor units and then turn them back on If error code 21 22 24 or 27 is displayed there may be an incorrect setting Perform the remote controller setting again NOTE Wh...

Page 15: ...ted Indoor unit remote controller com munication error 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has there been a check for gas leaks re...

Page 16: ...rror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor...

Reviews: