background image

En-6

 CAUTION

Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to 
tighten the fl are nut correctly.

Tighten the fl are nuts with a torque wrench using the specifi ed tightening method. Oth-
erwise, the fl are nuts could break after a prolonged period, causing refrigerant to leak 
and generate a hazardous gas if the refrigerant comes into contact with a fl ame.

Tighten with 2 wrenches.

Holding wrench

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut 

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

4.4. Installing heat insulation

 CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), per-
form this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 
so may cause water leaks.

After checking for gas leaks, insulate by wrapping insulation around the 2 parts (gas and 
liquid) of the indoor unit coupling, using the Coupler Heat Insulation.
After installing the Coupler Heat Insulation, wrap both ends with vinyl tape so that there is 
no gap.

Coupler heat insulation

Coupler heat 
insulation

Be sure to overlap the 
insulation

No gap

Body

 CAUTION

Must fi t tightly against body without any gap.

5.   ELECTRICAL WIRING

Cable

Cable size (mm

2

)

Type

Remarks

Connection cable

1.5 (MIN.)

Type 60245 IEC57

Earth (Ground), 

1

φ

230V

Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage 
drop is 2% or more.

For simultaneous multi

Conductor size (mm

2

)

Max length (m)

Bus wire

0.3 (MIN.)

500*

*This length shall be the total extended length in the system of the group.

(Total length of bus wire and remote controller cable.)

 WARNING

Electrical work must be performed in accordance with this Manual by a person certifi ed 
under the national or regional regulations. Be sure to use a dedicated circuit for the unit. 
An insuffi cient power supply circuit or improperly performed electrical work can cause 
serious accidents such as electric shock or fi re.

Before starting work, check that power is not being supplied to the indoor unit and 
outdoor unit.

Use the included transmission cables and power cables or ones specifi ed by the 
manufacturer. Improper connections, insuffi cient insulation, or exceeding the allowable 
current can cause electric shock or fi re.

For wiring, use the prescribed type of wires, connect them securely, making sure that 
there are no external forces of the wires applied to the terminal connections. Improp-
erly connected or secured wires can cause serious accidents such as overheating the 
terminals, electric shock, or fi re.

Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insuffi cient insulation, or exceeding the allowable current can 
cause electric shock or fi re.

Match the terminal block numbers and connection cable colors with those of the outdoor 
unit or branch box. Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal blocks. In addition, secure the 
cables with wiring holders. Improper connections, either in the wiring or at the ends of 
the wiring, can cause a malfunction, electric shock, or fi re.

Always fasten the outside covering of the connection cable with the cable clamp. (If the 
insulator is chafed, electric leakage may occur.)

Securely install the electrical box cover on the unit. An improperly installed electrical box 
cover can cause serious accidents such as electric shock or fi re through exposure to 
dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 
could result.

Install a earth (ground) leakage breaker. In addition, install the earth (ground) leakage 
breaker so that the entire AC main power supply is cut off at the same time. Otherwise, 
electric shock or fi re could result.

Always connect the earth (ground) wire.
Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cable and bus wire so as not to be direct touched with your 
hand.

(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to 

the terminal block.

(2) Securely clamp the ring terminals to the wires using an appropriate tool so that the 

wires do not come loose.

(3) Use the specifi ed wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 
screws from being properly tightened.

(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table 1 for the terminal screw tightening torques.

Strip 10 mm

Sleeve

Ring terminal

Screw with
special washer

Screw with
special washer

Ring terminal

Ring 
terminal

Wire

Wire

Terminal block

Terminal 
board

Table 1

Tightening torque

M4 screw

1.2 to 1.8 N·m (12 to 18 kgf·cm)

 WARNING

Use crimp-type terminals and tighten the terminal screws to the specifi ed torques, 
otherwise, abnormal overheating may be produced and possibly cause heavy 
damage inside the unit.

9379124010-05_IM.indb   6

9379124010-05_IM.indb   6

8/31/2012   10:43:21 AM

8/31/2012   10:43:21 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for AUYG14LVLB

Page 1: ...βις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Cassette Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ü T й и к с с у Р PART NO 9379124010 05 9379124010 ...

Page 2: ...eration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area Touching the refrigerant directly can c...

Page 3: ...ssette grille Hook wire 2 For suspending the Cassette grille Screw pitch small M4 10 mm 2 For mounting the Hook Wire for metals Screw pitch large M4 10 mm 4 For mounting the L angle and Hook wire for resins 2 5 Optional parts Parts name Model No Summary Wired remote controller UTY RNN M Unit control is performed by wired remote controller Simple Remote Controller UTY RSN M For air conditioner oper...

Page 4: ...ong and durable ceiling 262 or more 1 000 or more 1 800 or more 1 000 or more Unit mm Floor Obstruction This product can be installed at a height of up to 3 000mm However 7000 9000 Btu h model can not be installed in high places Perform the Function Setting on the remote control in accordance with the installed height See 8 2 Function setting Discharge direction setting The discharge direction can...

Page 5: ...p Air bleeding When lifting up drain Height of inclined pipe should be less than 700 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 mm or less from the unit 300 mm or less VP25 O D 32 mm local arrangement 700 mm or less Horizontal or upward gradient Downward gradient 1 100 to 1 50 VP30 O D 38 mm or more Downward gradient 1...

Page 6: ...flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other fla...

Page 7: ...nnections Improp erly connected or secured wires can cause serious accidents such as overheating the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with ...

Page 8: ...R UNIT R W B Red White Black Wired remote controller cable Indoor unit Remote controller cable Earth Ground the remote controller if it has a earth ground line Wired remote controller R W B Simultaneous twin 18 22 24 type only Connection cable Indoor unit Primary Indoor unit Secondary Junction box Lo cal purchase Outdoor unit Earth Ground line Control line Power line Earth Ground line Wired remote...

Page 9: ...ires Power supply cable or connection cable 20 mm 40mm or more Earth ground wire Use a 4 core wire cable 5 3 Connection of wiring 1 Remove the control box cover and install each connection wire Screw Control box cover 2 After wiring is complete secure the remote controller cable and transmission cable with the attached the cable tie and the clamper Detail a a Wire clamper accessory Bind securely T...

Page 10: ... Select a place that will not be affected by the heat from a stove etc Install the remote controller with a distance of 7 m between the remote controller and the photocell as the criteria However when installing the remote controller check that it operates positively Install the remote controller holder to a wall pillar etc with the tapping screw Mount the holder 1 Screws Set the remote controller...

Page 11: ...through the normal process refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE 1 Press the SET TEMP button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 2 Press the TIMER MODE button and check that the indoor unit can receive signals at ...

Page 12: ...or or remote controller unit sensor 8 Wireless remote controller signal code Change the indoor unit Signal Code depending on the wireless remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 9 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operati...

Page 13: ...supply cable Bus wire Remote controller cable Indoor unit 1 primary Indoor unit 2 secondary Indoor unit 3 secondary Set the R C address DIP switc h setting 2 Set the R C address of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set to make the R C address 00 Indoor unit R C address DIP SWITCH No 1 2 3 4 1 00...

Page 14: ...roller setting 4 Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 After completing the function settings turn off all of the indoor units and then turn them back on If error code 21 22 24 or 27 is displayed there may be an incorrect setting Perform the remote controller setting again NOTE Wh...

Page 15: ...ted Indoor unit remote controller com munication error 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has there been a check for gas leaks re...

Page 16: ...rror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor...

Reviews: