En-4

 

Special nut A

After installing the 
body, tighten the nuts.

Hook

Ceiling

Unit : mm

30 
or more

Special nut B

Hanging bolt

3.3.3. Leveling

Using a level, or vinyl hose fi lled with water, fi ne adjust so that the body is level.
Inclined installation so as the drain pipe side is higher may cause a malfunction of the fl oat 
switch, and may cause water leakage.

Vinyl hoses

Drain pipe

3.3.4. Installing drain pipe

 WARNING

Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat ex-
change erosion may occur)

Insulate the parts properly so that water will not drip from the connection parts.

Check for proper drainage after installation by using the visible portion of transparent 
drain port and the drain piping fi nal outlet on the body.

 CAUTION

Do not apply adhesive agent on the drain port of the body. (Use the attached drain 
hose assembly to connect the drain piping)

Note: Install the drain pipe.

•  Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or 

traps in the pipe.

•  Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32mm] and connect it 

with adhesive (polyvinyl chloride) so that there is no leakage.

•  When the pipe is long, install supporters.
• Do not perform air bleeding.
• Always heat insulate indoor section of drain pipe.
•  If it is impossible to have suffi cient gradient of pipe, perform drain lift-up.

Pipe size

Drain pipe

VP25 (O.D. 32 mm)

Hanging fi ttings

1.5 to 2 m

VP25 (O.D. 32 mm)
Downward gradient 1/100 to 1/50

Rise

PROHIBITED:

Trap

Air bleeding

When lifting up drain:

•  Height of inclined pipe should be less than 700 mm from the ceiling. A rise dimension 

over this range will cause leakage.

•  Lift up the pipe vertically at the position of 300 mm or less from the unit.

300 mm or less

VP25 (O.D. 32 mm)
local arrangement

700 mm or less

Horizontal or 
upward gradient

Downward gradient 
1/100 to 1/50

VP30 (O.D. 38 mm) or more 
Downward gradient 1/100 to 1/50

700 mm or less

Installation procedure

1) Install the attached drain hose to the drain port of the body. Install the hose band from 

the top of the hose within the shown in the fi gure area.

2) Use vinyl adhesive agent to glue the drain piping (PVC pipe VP25 ) to the drain hose 

assembly.

 

(Apply color adhesive agent evenly until the gauge line and seal)

3) Check the drainage. (See separate diagram)
4) Install the heat insulation.
5) Use the attached heat insulation to insulate the drain port and hose band.

Install the knob facing upward

Attach hose band 
(Accessories)

Locally installed 

PCV pipe

Attach drain hose

(Accessories)

Attach heat insulation 
(Accessories)

・ 

(a) Top view

(c) Hose opening view

Top view

(b) Side view

Hose band

19

Applying area 
of adhesive 35

Unit: mm

Gauge line

4 or less 

20 Transparent 
visible portion

Make sure there 
are no gaps

Wind the attached heat insulation 
around the hose band

Make sure the alignment is 
on top 

5~10

20

Note)
Check for drainage

Pour about 1 liter of water from the position (see 9. TEST RUN/CHECKING DRAINAGE). 
Check for any abnormalities such as strange noises and whether the drain pump functions 
normally

9379124010-05_IM.indb   4

9379124010-05_IM.indb   4

8/31/2012   10:43:18 AM

8/31/2012   10:43:18 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for AUYG14LVLB

Page 1: ...βις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Cassette Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ü T й и к с с у Р PART NO 9379124010 05 9379124010 ...

Page 2: ...eration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area Touching the refrigerant directly can c...

Page 3: ...ssette grille Hook wire 2 For suspending the Cassette grille Screw pitch small M4 10 mm 2 For mounting the Hook Wire for metals Screw pitch large M4 10 mm 4 For mounting the L angle and Hook wire for resins 2 5 Optional parts Parts name Model No Summary Wired remote controller UTY RNN M Unit control is performed by wired remote controller Simple Remote Controller UTY RSN M For air conditioner oper...

Page 4: ...ong and durable ceiling 262 or more 1 000 or more 1 800 or more 1 000 or more Unit mm Floor Obstruction This product can be installed at a height of up to 3 000mm However 7000 9000 Btu h model can not be installed in high places Perform the Function Setting on the remote control in accordance with the installed height See 8 2 Function setting Discharge direction setting The discharge direction can...

Page 5: ...p Air bleeding When lifting up drain Height of inclined pipe should be less than 700 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 mm or less from the unit 300 mm or less VP25 O D 32 mm local arrangement 700 mm or less Horizontal or upward gradient Downward gradient 1 100 to 1 50 VP30 O D 38 mm or more Downward gradient 1...

Page 6: ...flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other fla...

Page 7: ...nnections Improp erly connected or secured wires can cause serious accidents such as overheating the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with ...

Page 8: ...R UNIT R W B Red White Black Wired remote controller cable Indoor unit Remote controller cable Earth Ground the remote controller if it has a earth ground line Wired remote controller R W B Simultaneous twin 18 22 24 type only Connection cable Indoor unit Primary Indoor unit Secondary Junction box Lo cal purchase Outdoor unit Earth Ground line Control line Power line Earth Ground line Wired remote...

Page 9: ...ires Power supply cable or connection cable 20 mm 40mm or more Earth ground wire Use a 4 core wire cable 5 3 Connection of wiring 1 Remove the control box cover and install each connection wire Screw Control box cover 2 After wiring is complete secure the remote controller cable and transmission cable with the attached the cable tie and the clamper Detail a a Wire clamper accessory Bind securely T...

Page 10: ... Select a place that will not be affected by the heat from a stove etc Install the remote controller with a distance of 7 m between the remote controller and the photocell as the criteria However when installing the remote controller check that it operates positively Install the remote controller holder to a wall pillar etc with the tapping screw Mount the holder 1 Screws Set the remote controller...

Page 11: ...through the normal process refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE 1 Press the SET TEMP button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 2 Press the TIMER MODE button and check that the indoor unit can receive signals at ...

Page 12: ...or or remote controller unit sensor 8 Wireless remote controller signal code Change the indoor unit Signal Code depending on the wireless remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 9 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operati...

Page 13: ...supply cable Bus wire Remote controller cable Indoor unit 1 primary Indoor unit 2 secondary Indoor unit 3 secondary Set the R C address DIP switc h setting 2 Set the R C address of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set to make the R C address 00 Indoor unit R C address DIP SWITCH No 1 2 3 4 1 00...

Page 14: ...roller setting 4 Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 After completing the function settings turn off all of the indoor units and then turn them back on If error code 21 22 24 or 27 is displayed there may be an incorrect setting Perform the remote controller setting again NOTE Wh...

Page 15: ...ted Indoor unit remote controller com munication error 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has there been a check for gas leaks re...

Page 16: ...rror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor...

Reviews: