En-3

 CAUTION

Do not install the indoor unit in the following areas:

Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

• 

causing the parts to fail or the unit to leak water.
Area fi lled with mineral oil or containing a large amount of splashed oil or steam, such 

• 

as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak 
water. 
Area that generates substances that adversely affect the equipment, such as sulfuric 

• 

gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to 
corrode, which can cause refrigerant leakage. 
Area that can cause combustible gas to leak, contains suspended carbon fi bers or 

• 

fl ammable dust, or volatile infl ammables such as paint thinner or gasoline. If gas leaks 
and settles around the unit, it can cause a fi re.
Area where animals may urinate on the unit or ammonia may be generated.

• 

Do not install where there is the danger of combustible gas leakage.

Do not install the unit near a source of heat, steam, or fl ammable gas.

Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote 
control cable at least 1 m away from a television or radio receivers. The purpose of this 
is to prevent TV reception interference or radio noise. (Even if they are installed more 
than 1 m apart, you could still receive noise under some signal conditions.)

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

 Install the indoor unit in a location having suffi cient strength to support the weight of 

(1) 

the indoor unit.
 The inlet and outlet ports should not be obstructed; the air should be able to blow all 

(2) 

over the room.
Leave the space required to service the air conditioner.

(3) 

Locate where the air can be distributed evenly throughout the room by the unit.

(4) 

Install the unit where connection to the outdoor unit is easy. 

(5) 

Install the unit where the connection pipe can be easily installed. 

(6) 

Install the unit where the drain pipe can be easily installed.

(7) 

Install the unit where noise and vibration is not amplifi ed. 

(8) 

 Take servicing, etc., into consideration and leave the spaces. Also install the unit 

(9) 

where the fi lter can be removed.

3.2. Installation dimension

The ceiling rear height as shown in the fi gure.

• 

Strong and durable ceiling

262 
or more 

1,000
or more 

1,800 

or more 

1,000 

or more 

Unit : mm

Floor

Obstruction

This product can be installed at a height of up to 3,000mm.

• 

However, 7000, 9000 Btu/h model can not be installed in high places.

Perform the Function Setting on the remote control in accordance with the installed height. 
(See 8.2.Function setting)

Discharge direction setting

The discharge direction can be selected as shown below.

• 

100 or more*

(4 directions)

(3 directions) 

Unit : mm

*Please ensure 

suffi cient 
service access 
during installation.

For a 3-way outlet, make sure to perform the Function Setting on the remote control. 

• 

Also, make sure to use the optional shutter plate to block the outlet.

The ceiling height cannot be set in the 3-way outlet mode. Therefore, do not change the 

• 

setting in the setting the ceiling height. (See 

8.2. FUNCTION SETTING

)

When the outlet is shut, be sure to install the optional Air outlet shutter plate kit.

• 

For the details of installation, please refer to Installation Manual of kit.

3.3. Installation the unit

 WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times the 
weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

If the job is done with the panel frame only, there is a risk that the unit will come loose. 
Please take care.

3.3.1. Position the ceiling hole and hanging bolts

Ceiling openings and hanging bolt installation diagram.

WARNING

When fastening the hangers, make the bolt positions uniform.

530 (Hanging bolt position)

service access

250

99

40

102

215

30

58

123

11

4

30

262

250

75

150~200

Drain pipe (O.D.ø26.1)

Ceiling

Control box

Liquid pipe Gas pipe

Unit : mm

540 (Hanging bolt position)

 570(Indoor unit)

580 – 660 (Ceiling openings)

700 (Cassette Grille)

Min.450

Min.450

Be sure to keep suffi cient space in the designated position for future maintenance.

3.3.2. Body installation

(1) Install special nut A, then special nut B onto the hanging bolt.
(2) Raise the body and mount its hooks onto the hanging bolt between the special nuts.
(3)Turn special nut B to adjust the height of the body.

 WARNING

Perform fi nal tightening by tightening the double nut fi rmly.

Be sure to install the body horizontally and adjust the height below the body and the 
ceiling surface properly.

9379124010-05_IM.indb   3

9379124010-05_IM.indb   3

8/31/2012   10:43:17 AM

8/31/2012   10:43:17 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for AUYG14LVLB

Page 1: ...βις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Cassette Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ü T й и к с с у Р PART NO 9379124010 05 9379124010 ...

Page 2: ...eration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area Touching the refrigerant directly can c...

Page 3: ...ssette grille Hook wire 2 For suspending the Cassette grille Screw pitch small M4 10 mm 2 For mounting the Hook Wire for metals Screw pitch large M4 10 mm 4 For mounting the L angle and Hook wire for resins 2 5 Optional parts Parts name Model No Summary Wired remote controller UTY RNN M Unit control is performed by wired remote controller Simple Remote Controller UTY RSN M For air conditioner oper...

Page 4: ...ong and durable ceiling 262 or more 1 000 or more 1 800 or more 1 000 or more Unit mm Floor Obstruction This product can be installed at a height of up to 3 000mm However 7000 9000 Btu h model can not be installed in high places Perform the Function Setting on the remote control in accordance with the installed height See 8 2 Function setting Discharge direction setting The discharge direction can...

Page 5: ...p Air bleeding When lifting up drain Height of inclined pipe should be less than 700 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 mm or less from the unit 300 mm or less VP25 O D 32 mm local arrangement 700 mm or less Horizontal or upward gradient Downward gradient 1 100 to 1 50 VP30 O D 38 mm or more Downward gradient 1...

Page 6: ...flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other fla...

Page 7: ...nnections Improp erly connected or secured wires can cause serious accidents such as overheating the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with ...

Page 8: ...R UNIT R W B Red White Black Wired remote controller cable Indoor unit Remote controller cable Earth Ground the remote controller if it has a earth ground line Wired remote controller R W B Simultaneous twin 18 22 24 type only Connection cable Indoor unit Primary Indoor unit Secondary Junction box Lo cal purchase Outdoor unit Earth Ground line Control line Power line Earth Ground line Wired remote...

Page 9: ...ires Power supply cable or connection cable 20 mm 40mm or more Earth ground wire Use a 4 core wire cable 5 3 Connection of wiring 1 Remove the control box cover and install each connection wire Screw Control box cover 2 After wiring is complete secure the remote controller cable and transmission cable with the attached the cable tie and the clamper Detail a a Wire clamper accessory Bind securely T...

Page 10: ... Select a place that will not be affected by the heat from a stove etc Install the remote controller with a distance of 7 m between the remote controller and the photocell as the criteria However when installing the remote controller check that it operates positively Install the remote controller holder to a wall pillar etc with the tapping screw Mount the holder 1 Screws Set the remote controller...

Page 11: ...through the normal process refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE 1 Press the SET TEMP button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 2 Press the TIMER MODE button and check that the indoor unit can receive signals at ...

Page 12: ...or or remote controller unit sensor 8 Wireless remote controller signal code Change the indoor unit Signal Code depending on the wireless remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 9 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operati...

Page 13: ...supply cable Bus wire Remote controller cable Indoor unit 1 primary Indoor unit 2 secondary Indoor unit 3 secondary Set the R C address DIP switc h setting 2 Set the R C address of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set to make the R C address 00 Indoor unit R C address DIP SWITCH No 1 2 3 4 1 00...

Page 14: ...roller setting 4 Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 After completing the function settings turn off all of the indoor units and then turn them back on If error code 21 22 24 or 27 is displayed there may be an incorrect setting Perform the remote controller setting again NOTE Wh...

Page 15: ...ted Indoor unit remote controller com munication error 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has there been a check for gas leaks re...

Page 16: ...rror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor...

Reviews: