En-11
(
¡
... Factory setting)
Setting description
Function number
Setting value
Standard (2,500 hours)
11
00
Long interval (4,400 hours)
01
Short interval (1,250 hours)
02
¡
No indication
03
(2) Ceiling height
Select the setting values in the table below according to the height of the ceiling.
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
Standard
(2.7 m [9 ft])
20
00
High ceiling
(3.0 m [10 ft])
01
* However, 7000, 9000 Btu/h model can not be installed in high places.
(3) Outlet directions
Select the setting values in the table below for using a 3-way outlet.
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
4-way
22
00
3-way
01
(4) Cooling room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below.
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
Standard
30
00
Slightly lower control
01
Lower control
02
Warmer control
03
(5) Heating room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below.
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
(6) Auto restart
Enable or disable automatic system restart after a power outage.
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
Yes
40
00
No
01
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
(7) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed using the Wired remote controller temperature sensor
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
No
42
00
Yes
01
* If setting value is “00”:
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01”:
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
(8) Wireless remote controller signal code
Change the indoor unit Signal Code, depending on the wireless remote controllers.
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
A
44
00
B
01
C
02
D
03
(9) External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(
¡
... Factory setting)
Setting description
Function number
Setting value
¡
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
Setting record
•
Record any changes to the settings in the following table.
Setting
Setting Value
(1) Filter sign
(2) Ceiling height
(3) Outlet directions
(4) Cooler room temperature correction
(5) Heater room temperature correction
(6) Auto restart
(7) Indoor room temperature sensor switching function
(8) Wireless remote controller signal code
(9) External input control
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
8.3. Selecting the remote controller signal code
[When using the wireless remote controller]
When 2 or more air conditioners are installed in a room and the remote controller is
operating an air conditioner other than the one you wish to set, change the signal code
of the remote controller to operate only the air conditioner you wish to set (4 selections
possible).
When 2 or more air conditioners are installed in a room, please contact your retailer to set
the individual air conditioner signal codes.
Confi rm the setting of the remote controller signal code and the printed circuit board
setting.
If these are not confi rmed, the remote controller cannot be used to operate for the air
conditioner.
Selecting the Remote Controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note that the
air conditioner cannot receive a signal code if the air conditioner has not been set for the
signal code.)
(1) Press the START/STOP button until only the clock is displayed on the remote control-
ler display.
(2) Press the MODE button for at least 5 seconds to display the current signal code
(initially set to
).
(3) Press the SET TEMP. (
▲
) (
▼
) button to change the signal code between
. Match the code on the display to the air conditioner signal code.
9379124010-05_IM.indb 11
9379124010-05_IM.indb 11
8/31/2012 10:43:31 AM
8/31/2012 10:43:31 AM