En-14

9. TEST RUN

CHECK ITEMS

Is operation of each button on the remote controller normal?

(1) 

Does each lamp light normally?

(2) 

Do not air fl ow direction louvers operate normally?

(3) 

Is the drain normal?

(4) 

Is there any error noise and vibration during operation?

(5) 

Do not operate the air conditioner test run for a long time.

• 

CHECKING DRAINAGE

To check the drain, remove the water cover and fi ll with 1 liter of water as shown in the 
fi gure.
The drain pump operates when operating in the cooling mode.

Drain pipe

Wire cover

Screw

Watering pot

• Test running

When the air conditioner is 

run by pressing the remote controller test run button, 

the OPERATION and TIMER lamps fl ash slowly at the same time.

[Operation method]

For the operation method, refer to the operating manual.

• 

The outdoor unit may not operate depending on the room temperature. 

• 

In this case, press the TEST RUN button on the remote controller while the air condi-
tioner is running. (Point the transmitter section of the remote controller toward the air 

conditioner and press the TEST RUN button with the tip of a ball-point pen, etc.)

Transmitter section

TEST RUN button

To end test operation, press the remote controller START/STOP button. 

• 

(When the air conditioner is run by pressing the TEST RUN button, the OPERATION 
Lamp and TIMER Lamp will simultaneously fl ash slowly.)

[Using the wired remote control] (Option)

For the operation method, refer to the operating manual.

• 

Stop the air conditioner operation.

(1) 

Press the MODE button and the FAN button simultaneously for 2 seconds or more to 

(2) 

start the test run.

Test run display

Press the START/STOP button to stop the test run.

(3) 

If “C0” appears in the R.C. address display, there is a remote controller error. Refer to the 
installation manual included with the remote controller.

R.C. address

Error code

Content

Incompatible indoor unit is connected

Indoor unit 

 remote controller com-

munication error

10. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s). After 
installation is complete, be sure to check the following check items again.

CHECK ITEMS

If not performed 

correctly

CHECK 

BOX

Has the indoor unit been installed 
correctly?

Vibration, noise, indoor unit 
may drop

Has there been a check for gas 
leaks (refrigerant pipes)?

No cooling, No heating

Has heat insulation work been 
completed?

Water leakage

Does water drain easily from the 
indoor units?

Water leakage

Are the wires and pipes all con-
nected completely?

No operation, heat or burn 
damage

Is the connection cable the speci-
fi ed thickness?

No operation, heat or burn 
damage

Are the inlets and outlets free of any 
obstacles?

No cooling, No heating

After installation is completed, has 
the proper operation and handling 
been explained to the user?

11. OPTIONAL KIT INSTALLATION (OPTION)

 WARNING

Regulation of cable differs from each locality, refer in accordance with local rules.

This air conditioner can be connected with the following optional kits.

Option type

Connector No.

Fresh air intake

CN6

External input

CN102

External output

CN103

Wired Remote Controller

-

Fresh air intake kit

Wired Remote Controller

External output kit

External input kit

12. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:

Starting and stopping method, operation switching, temperature adjustment, timer, air 

(1) 

fl ow switching, and other remote controller unit operations.

Air fi lter removal and cleaning, and how to use the air louvers.

(2) 

Give the operating and Installation Manuals to the customer.

(3) 

If the signal code is changed, explain to the customer how it changed (the system 

(4) 

returns to signal code A when the batteries in the remote controller unit are replaced).
*(4) is applicable to using wireless remote controller.

9379124010-05_IM.indb   14

9379124010-05_IM.indb   14

8/31/2012   10:43:35 AM

8/31/2012   10:43:35 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for AUYG14LVLB

Page 1: ...βις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Cassette Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ü T й и к с с у Р PART NO 9379124010 05 9379124010 ...

Page 2: ...eration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area Touching the refrigerant directly can c...

Page 3: ...ssette grille Hook wire 2 For suspending the Cassette grille Screw pitch small M4 10 mm 2 For mounting the Hook Wire for metals Screw pitch large M4 10 mm 4 For mounting the L angle and Hook wire for resins 2 5 Optional parts Parts name Model No Summary Wired remote controller UTY RNN M Unit control is performed by wired remote controller Simple Remote Controller UTY RSN M For air conditioner oper...

Page 4: ...ong and durable ceiling 262 or more 1 000 or more 1 800 or more 1 000 or more Unit mm Floor Obstruction This product can be installed at a height of up to 3 000mm However 7000 9000 Btu h model can not be installed in high places Perform the Function Setting on the remote control in accordance with the installed height See 8 2 Function setting Discharge direction setting The discharge direction can...

Page 5: ...p Air bleeding When lifting up drain Height of inclined pipe should be less than 700 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 mm or less from the unit 300 mm or less VP25 O D 32 mm local arrangement 700 mm or less Horizontal or upward gradient Downward gradient 1 100 to 1 50 VP30 O D 38 mm or more Downward gradient 1...

Page 6: ...flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other fla...

Page 7: ...nnections Improp erly connected or secured wires can cause serious accidents such as overheating the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with ...

Page 8: ...R UNIT R W B Red White Black Wired remote controller cable Indoor unit Remote controller cable Earth Ground the remote controller if it has a earth ground line Wired remote controller R W B Simultaneous twin 18 22 24 type only Connection cable Indoor unit Primary Indoor unit Secondary Junction box Lo cal purchase Outdoor unit Earth Ground line Control line Power line Earth Ground line Wired remote...

Page 9: ...ires Power supply cable or connection cable 20 mm 40mm or more Earth ground wire Use a 4 core wire cable 5 3 Connection of wiring 1 Remove the control box cover and install each connection wire Screw Control box cover 2 After wiring is complete secure the remote controller cable and transmission cable with the attached the cable tie and the clamper Detail a a Wire clamper accessory Bind securely T...

Page 10: ... Select a place that will not be affected by the heat from a stove etc Install the remote controller with a distance of 7 m between the remote controller and the photocell as the criteria However when installing the remote controller check that it operates positively Install the remote controller holder to a wall pillar etc with the tapping screw Mount the holder 1 Screws Set the remote controller...

Page 11: ...through the normal process refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE 1 Press the SET TEMP button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 2 Press the TIMER MODE button and check that the indoor unit can receive signals at ...

Page 12: ...or or remote controller unit sensor 8 Wireless remote controller signal code Change the indoor unit Signal Code depending on the wireless remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 9 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operati...

Page 13: ...supply cable Bus wire Remote controller cable Indoor unit 1 primary Indoor unit 2 secondary Indoor unit 3 secondary Set the R C address DIP switc h setting 2 Set the R C address of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set to make the R C address 00 Indoor unit R C address DIP SWITCH No 1 2 3 4 1 00...

Page 14: ...roller setting 4 Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 After completing the function settings turn off all of the indoor units and then turn them back on If error code 21 22 24 or 27 is displayed there may be an incorrect setting Perform the remote controller setting again NOTE Wh...

Page 15: ...ted Indoor unit remote controller com munication error 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has there been a check for gas leaks re...

Page 16: ...rror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor...