En-15
13. ERROR CODES
If you use a wireless remote controller, the lamp on the photo detector unit will output error
codes by way of blinking patterns. If you use a wired type remote controller, error codes
will appear on the remote controller display. See the lamp blinking patterns and error
codes in the table. An error display is displayed only during operation.
Error display
Wired
remote
controller
Error code
Description
OPERA-
TION lamp
(green)
TIMER
lamp
(orange)
ECONO-
MY lamp
(green)
●
(1)
●
(1)
◊
Serial communication error
●
(1)
●
(2)
◊
Wired remote controller
communication error
●
(1)
●
(5)
◊
Check run unfi nished
●
(2)
●
(1)
◊
R.C. address or Refrigerant circuit
address setting error
[Simultaneous Multi]
●
(2)
●
(2)
◊
Indoor unit capacity error
●
(2)
●
(3)
◊
Combination error
●
(2)
●
(4)
◊
Connection R.C. address
•
error (indoor secondary unit)
[Simultaneous Multi]
Connection R.C. address error
•
(indoor unit or branch unit) [Flex-
ible Multi]
●
(2)
●
(7)
◊
Primary unit, secondary unit set-
up error [Simultaneous Multi]
●
(3)
●
(1)
◊
Power supply interruption error
●
(3)
●
(2)
◊
Indoor unit PCB model
information error
●
(3)
●
(5)
◊
Manual auto switch error
●
(4)
●
(1)
◊
Inlet air temp. sensor error
●
(4)
●
(2)
◊
Indoor unit Heat Ex. Middle temp.
sensor error
●
(5)
●
(1)
◊
Indoor unit fan motor error
●
(5)
●
(3)
◊
Drain pump error
●
(5)
●
(7)
◊
Damper error
●
(5)
●
(15)
◊
Indoor unit error
●
(6)
●
(2)
◊
Outdoor unit main PCB model
information error or
communication error
●
(6)
●
(3)
◊
Inverter error
●
(6)
●
(4)
◊
Active fi lter error, PFC circuit error
●
(6)
●
(5)
◊
Trip terminal L error
●
(6)
●
(10)
◊
Display PCB microcomputers
communication error
●
(7)
●
(1)
◊
Discharge temp. sensor error
●
(7)
●
(2)
◊
Compressor temp. sensor error
●
(7)
●
(3)
◊
Outdoor unit Heat Ex. liquid temp.
sensor error
●
(7)
●
(4)
◊
Outdoor temp. sensor error
●
(7)
●
(5)
◊
Suction Gas temp. sensor error
●
(7)
●
(6)
◊
2-way valve temp. sensor error
•
3-way valve temp. sensor error
•
●
(7)
●
(7)
◊
Heat sink temp. sensor error
●
(8)
●
(2)
◊
Sub-cool Heat Ex. gas inlet
•
temp. sensor error
Sub-cool Heat Ex. gas outlet
•
temp. sensor error
●
(8)
●
(3)
◊
Liquid pipe temp. sensor error
●
(8)
●
(4)
◊
Current sensor error
●
(8)
●
(6)
◊
Discharge pressure sensor error
•
Suction pressure sensor error
•
High pressure switch error
•
●
(9)
●
(4)
◊
Trip detection
●
(9)
●
(5)
◊
Compressor rotor position
detection error (permanent stop)
●
(9)
●
(7)
◊
Outdoor unit fan motor 1 error
●
(9)
●
(8)
◊
Outdoor unit fan motor 2 error
●
(9)
●
(9)
◊
4-way valve error
●
(9)
●
(10)
◊
Coil (expansion valve ) error
●
(10)
●
(1)
◊
Discharge temp. error
●
(10)
●
(3)
◊
Compressor temp. error
●
(10)
●
(4)
◊
High pressure error
●
(10)
●
(5)
◊
Low pressure error
●
(13)
●
(2)
◊
Branch boxes error
[Flexible Multi]
Display mode
●
: 0.5s ON / 0.5s OFF
◊
: 0.1s ON / 0.1s OFF
( ) : Number of fl ashing
[Troubleshooting with the indoor unit display]
ECONOMY Lamp
(GREEN)
TIMER Lamp
(ORANGE)
OPERATION Lamp
(GREEN)
MANUAL AUTO
[Troubleshooting at the remote controller LCD]
This is possible only on the wired remote controller.
[Self-diagnosis]
If an error occurs, the following display will be shown.
(“Er” will appear in the set room temperature display.)
R.C. address
Error code
EX. Self-diagnosis
9379124010-05_IM.indb 15
9379124010-05_IM.indb 15
8/31/2012 10:43:37 AM