En-10
(2) Connect the connector.
Wire (louver): WHITE
Wire (display): WHITE
Wire (louver): RED
Indoor unit side
Arrange the wires as illustrated below.
•
(3) Attach the connector cover.
Screw
Connector cover
7.3. Attach the intake grille
The installation is the reverse of “REMOVING THE INTAKE GRILLE”.
The intake grille can be rotated and installed 4 ways to suit the user’s preference.
CAUTION
The louver angle cannot be changed if the power is not on. (If moved by hand, it may
be damaged.)
The grille assembly is directionally relative to the air conditioner body.
Install so that there is no gap between the grille assembly and the air conditioner body.
The cassette grille equips with an accessory to prevent the grill completely open. Be
sure to read the INSTALLATION SHEET included with the cassette grille before instal-
lation.
8. FUNCTION SETTING
CAUTION
Confi rm whether the wiring work for outdoor unit has been fi nished.
Confi rm whether the cap for electric control box on the outdoor unit is close.
This procedure changes to the function settings used to control the indoor unit according
•
to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the instal-
•
lation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting
•
Value.
Settings will not be changed if invalid numbers or setting values are selected.
•
Refer to the installation manual enclosed with the remote controller when the wired
•
remote controller (option) is used.
8.1. Operation method
While pressing the FAN button and SET TEMP. (
•
) simultaneously, press the RESET
button to enter the function setting mode.
STEP 1
Selecting the Remote Controller Signal Code
Use the following steps to select the signal code of the remote controller.
(Note that the air conditioner cannot receive a signal code if the air conditioner has not
been set for the signal code.)
The signal codes that are set through this process are applicable only to the signals in
the FUNCTION SETTING. For details on how to set the signal codes through the normal
process, refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE.
(1) Press the SET TEMP. (
) (
) button to change the signal code between
.
Match the code on the display to the air conditioner signal code. (initially set to
) (If
the signal code does not need to be selected, press the MODE button and proceed to
STEP 2.)
(2) Press the TIMER MODE button and check that the indoor unit can receive signals at
the displayed signal code.
(3) Press the MODE button to accept the signal code, and proceed to STEP 2.
The air conditioner signal code is factory-set to A .
Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller
are replaced. If you use a signal code other than signal code A, reset the signal code
after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes
(
) until you fi nd the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
(1) Press the SET TEMP. (
) (
) buttons to select the function number. (Press the
MODE button to switch between the left and right digits.)
(2) Press the FAN button to proceed to setting the value. (Press the FAN button again to
return to the function number selection.)
(3) Press the SET TEMP. (
) (
) buttons to select the setting value. (Press the MODE
button to switch between the left and right digits.)
(4) Press the TIMER MODE button, and START/STOP button, in the order listed to
confi rm the settings.
(5) Press the RESET button to cancel the function setting mode.
(6) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
Function number
Setting value
CAUTION
After turning off the power, wait 30 seconds or more before turning on it again. The
FUNCTION SETTING doesn’t become effective if it doesn’t do so.
8.2. Function setting
(1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the fi lter. Select the
time setting for the fi lter sign display interval in the table below according to the amount
of dust or debris in the room. If you do not wish the fi lter sign to be displayed, select the
setting value for “No indication”.