background image

En-13

8.4.2. Group control system

 CAUTION

Group control cannot be used when using it by the fl exible multi type.

A number of indoor units can be operated at the same time using a single remote controller.

 

(1)  Wiring method (indoor unit to remote controller)

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

Indoor 
unit 

1

Bus wire

Remote 
controller cable

Remote controller

When earth (ground) wire is necessary

Indoor 
unit 

2

Indoor 
unit 

3

Indoor 
unit 

4

  Set the R.C. address (DIP switch setting)

(2) 

Set the R.C. address of each indoor unit using the DIP switches on the indoor unit 
circuit board. (See the following table and fi gure.)
The DIP switches are normally set to make the R.C. address 00.

Indoor unit

R.C. address

DIP SWITCH No.

1

2

3

4

00

OFF

OFF

OFF

OFF

01

ON

OFF

OFF

OFF

02

OFF

ON

OFF

OFF

03

ON

ON

OFF

OFF

04

OFF

OFF

ON

OFF

05

ON

OFF

ON

OFF

06

OFF

ON

ON

OFF

07

ON

ON

ON

OFF

08

OFF

OFF

OFF

ON

09

ON

OFF

OFF

ON

10

OFF

ON

OFF

ON

11

ON

ON

OFF

ON

12

OFF

OFF

ON

ON

13

ON

OFF

ON

ON

14

OFF

ON

ON

ON

15

ON

ON

ON

ON

NOTE

Be sure to set the R.C. address sequentially.

 

 

 

 

 

 

 

 

00

01

02

03

R.C address

(DIP switch setting)

Remote 
controller

: Transmission cable, Power supply cable

: Power supply cable

: Bus wire

: Remote controller cable

Outdoor 
unit 

1

Indoor 
unit 

1

Indoor 
unit 

2

Indoor 
unit 

3

Indoor 
unit 

4

Outdoor 
unit 

2

Outdoor 
unit 

3

Outdoor 
unit 

4

Settings when simultaneous Multi is included

Set the refrigerant circuit address (Remote controller setting)

(3) 

Turn on all of the indoor units.

1. 

*  Turn on the indoor unit with the R.C. address 00 last.

(Within 1 minute)

Set the refrigerant circuit address.

2. 

Assign the same number to all of the indoor units connected to an outdoor unit.

(The unit is factory-set to “00”)

Refrigerant circuit address

Function Number

Setting Value

00

02

00

15

01

14

15

Set the “primary” and “secondary” settings. (Remote controller setting)

(4) 
(Set the indoor unit that is connected to the outdoor unit using a transmission cable as the 
“primary”.)

Function Number

Setting Value

Primary

51

00

Secondary

01

After completing the function settings, turn off all of the indoor units, 
and then turn them back on.
*  If error code 21, 22, 24, or 27 is displayed, there may be an incorrect 

setting. Perform the remote controller setting again.

NOTE

When different indoor unit models are connected using the group control system, some 

• 

functions may no longer be available.
If the group control system contains multiple units that are operated simultaneously, con-

• 

nect and set the units as shown below.
Auto-changeover operates under the same mode with model R.C. address 00.

• 

It should not be connected to any other Gr that is not of the same series (A**G only).

• 

R.C address

Standard 

pair

Standard 

pair

Simultaneous 

twin

Simultaneous 

triple

Refrigerant circuit 
address setting

Primary/Secondary setting

(DIP switch setting)

(Function number 02)

(Function number 51)

Remote 
controller

: Transmission cable, Power supply cable

: Power supply cable

: Bus wire

: Remote controller cable

Outdoor 
unit 

1

Outdoor 
unit 

2

Outdoor 
unit 

3

Outdoor 
unit 

4

Indoor 
unit 

1

Indoor 
unit 

2

Indoor 
unit 

3

Indoor 
unit 

4

Indoor 
unit 

5

Indoor 
unit 

6

Indoor 
unit 

7

8.4.3. Dual remote controllers

2 separate remote controllers can be used to operate the indoor units.

• 

The timer and self-diagnosis functions cannot be used on the secondary unit of remote 

• 

controller.

 Wiring method (indoor unit to remote controller)

(1) 

1 2 3

1 2 3

1 2 3

Indoor unit

Secondary unit

Primary unit

Remote controller cable

Remote 
controller

Remote 
controller

When earth (ground) wire 
is necessary

 Remote controller DIP switch 1 setting 

(2) 

Set the remote controller DIP switch 1-No. 2 according to the following table.

DIP SW 1-No. 2

Primary unit

OFF

Secondary unit

ON

9379124010-05_IM.indb   13

9379124010-05_IM.indb   13

8/31/2012   10:43:33 AM

8/31/2012   10:43:33 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for AUYG14LVLB

Page 1: ...βις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Cassette Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ü T й и к с с у Р PART NO 9379124010 05 9379124010 ...

Page 2: ...eration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refrigerant pipe connections or other area Touching the refrigerant directly can c...

Page 3: ...ssette grille Hook wire 2 For suspending the Cassette grille Screw pitch small M4 10 mm 2 For mounting the Hook Wire for metals Screw pitch large M4 10 mm 4 For mounting the L angle and Hook wire for resins 2 5 Optional parts Parts name Model No Summary Wired remote controller UTY RNN M Unit control is performed by wired remote controller Simple Remote Controller UTY RSN M For air conditioner oper...

Page 4: ...ong and durable ceiling 262 or more 1 000 or more 1 800 or more 1 000 or more Unit mm Floor Obstruction This product can be installed at a height of up to 3 000mm However 7000 9000 Btu h model can not be installed in high places Perform the Function Setting on the remote control in accordance with the installed height See 8 2 Function setting Discharge direction setting The discharge direction can...

Page 5: ...p Air bleeding When lifting up drain Height of inclined pipe should be less than 700 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 mm or less from the unit 300 mm or less VP25 O D 32 mm local arrangement 700 mm or less Horizontal or upward gradient Downward gradient 1 100 to 1 50 VP30 O D 38 mm or more Downward gradient 1...

Page 6: ...flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other fla...

Page 7: ...nnections Improp erly connected or secured wires can cause serious accidents such as overheating the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with ...

Page 8: ...R UNIT R W B Red White Black Wired remote controller cable Indoor unit Remote controller cable Earth Ground the remote controller if it has a earth ground line Wired remote controller R W B Simultaneous twin 18 22 24 type only Connection cable Indoor unit Primary Indoor unit Secondary Junction box Lo cal purchase Outdoor unit Earth Ground line Control line Power line Earth Ground line Wired remote...

Page 9: ...ires Power supply cable or connection cable 20 mm 40mm or more Earth ground wire Use a 4 core wire cable 5 3 Connection of wiring 1 Remove the control box cover and install each connection wire Screw Control box cover 2 After wiring is complete secure the remote controller cable and transmission cable with the attached the cable tie and the clamper Detail a a Wire clamper accessory Bind securely T...

Page 10: ... Select a place that will not be affected by the heat from a stove etc Install the remote controller with a distance of 7 m between the remote controller and the photocell as the criteria However when installing the remote controller check that it operates positively Install the remote controller holder to a wall pillar etc with the tapping screw Mount the holder 1 Screws Set the remote controller...

Page 11: ...through the normal process refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE 1 Press the SET TEMP button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 2 Press the TIMER MODE button and check that the indoor unit can receive signals at ...

Page 12: ...or or remote controller unit sensor 8 Wireless remote controller signal code Change the indoor unit Signal Code depending on the wireless remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 9 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operati...

Page 13: ...supply cable Bus wire Remote controller cable Indoor unit 1 primary Indoor unit 2 secondary Indoor unit 3 secondary Set the R C address DIP switc h setting 2 Set the R C address of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set to make the R C address 00 Indoor unit R C address DIP SWITCH No 1 2 3 4 1 00...

Page 14: ...roller setting 4 Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 After completing the function settings turn off all of the indoor units and then turn them back on If error code 21 22 24 or 27 is displayed there may be an incorrect setting Perform the remote controller setting again NOTE Wh...

Page 15: ...ted Indoor unit remote controller com munication error 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has there been a check for gas leaks re...

Page 16: ...rror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor...

Reviews: