
Calibration
Asterion DC Series
3-62
3.9.2
Series Operation
Series operation is used to obtain a higher aggregate output voltage, the rated
voltage sum of the series supplies, using up to two power supplies. To connect two
power supplies in series, refer to Section 3.1.7.1 and use
a “Leader/ ollower” wiring
configuration as follows; refer to Figure 3-117. Series Connection. There are two
separate modular
connectors on the rear panel of each power supply, marked “PAR
OUT” and “PAR IN”. Also, there are two modular connectors on the rear panel of
each power supply, marked ‘CAN OUT” and “CAN IN".)
1. Programming, readback, and control is performed through the unit set as
Leader.
2. Beginning with the power supply that is to function as the Leader, use an
interface cable (890-524-01) to connect the PAR OUT connector on the
designated Leader power supply to the PAR IN connector on the second
power supply (Follower). Repeat connection between Leader CAN OUT and
Follower CAN IN also using cable 890-524-0.
3. Connect the Positive output terminal of the Leader power supply to the
positive terminal of the load.
4. Connect the Negative output terminal of the Leader power supply to the
Positive output terminal secondary unit (Follower).
5. Connect the Negative output terminal of the secondary unit (Follower) to the
negative terminal of the load.
6. Confirm that there are no shorts between the Positive and Negative output
terminals.
7. Referring to Figure 3-117, connect twisted-pair sense cables as follows;
ensure that all twisted-pair cables are as short as possible:
Both units (Leader and Follower) shall have twisted-pair cables from their
sense terminals to their own output terminals.
Note:
1.
The maximum allowable current for a series string of power supplies is the rated
output current of a single supply of the string.
2.
Remote sensing
at the load
should
not
be used during series operation. Each
power supply should have its remote sense leads connected to its own output
terminals.
3.
An anti-parallel diode (power diode capable of the maximum current of the series
group, connected across the output, but reverse biased) is recommended to
protect against sinking current into a supply should one supply be ON while
another other is OFF, as shown in Figure 3-116. Series Connection with Anti-
Parallel Diodes and Figure 3-117. Series Connection
Summary of Contents for Sorensen Asterion DC Series
Page 1: ...M330460 01 Rev D 1 Asterion DC Series Operation Manual...
Page 2: ...Contents Asterion DC Series ii This page intentionally left blank...
Page 23: ...Asterion DC Series Overview M330460 01 Rev D 1 7 Figure 1 2 Auto range Models Characteristics...
Page 38: ...Overview Asterion DC Series 1 22 This page intentionally left blank...
Page 43: ...Asterion DC Series Installation M330460 01 Rev D 2 5 Figure 2 1 Rack mounting 1U Models...
Page 44: ...Installation Asterion DC Series 2 6 Figure 2 2 Rack Mounting 2U Chassis...
Page 49: ...Asterion DC Series Installation M330460 01 Rev D 2 11 Figure 2 5 Rear Panel View 1U Models...
Page 50: ...Installation Asterion DC Series 2 12 Figure 2 6 Rear Panel View 1U Models w EtherCAT Option...
Page 52: ...Installation Asterion DC Series 2 14 Figure 2 8 Rear Panel View 2U Chassis...
Page 83: ...Asterion DC Series Installation M330460 01 Rev D 2 45 This page intentionally left blank...
Page 84: ......
Page 144: ...Calibration Asterion DC Series 3 60 Figure 3 114 Parallel Connection 3 Chassis...
Page 148: ...Calibration Asterion DC Series 3 64 Figure 3 117 Series Connection...
Page 149: ...Asterion DC Series Calibration M330460 01 Rev D 3 1 This page intentionally left blank...
Page 151: ...Asterion DC Series Calibration M330460 01 Rev D 4 3 This page intentionally left blank...
Page 152: ......
Page 157: ...M330460 01 www powerandtest com This page intentionally left blank...