APPENDIX C: SCR, WIRE GAUGE, AND CIRCUIT BREAKER SELECTION
STA SERIES AC CONTROLS
990-351
C-
3
Wire Gauges Based on Demand (kVA)
For wire gauge needed to support a maximum of 5% voltage drop, consult table C-4. The information
herein is based on NFPA70 National Electric Code table 9 in Chapter 9. The calculations are based on a
30% power factor and 100 foot power cable run.
Wire Gauge Based on Demand 240V AC Mains
Demand kVA
240
Max Zw
Max Rw
Max XLw
AWG (Cu)
10 42
2.880E-01
8.640E-01
2.758E+00
8
15 63
1.920E-01
5.760E-01
1.839E+00
6
20 83
1.440E-01
4.320E-01
1.379E+00
4
30 125
9.600E-02
2.880E-01
9.195E-01 3
50 208
5.760E-02
1.728E-01
5.517E-01 1
75 313
3.840E-02
1.152E-01
3.678E-01
2/0
100 417
2.880E-02
8.640E-02
2.758E-01 3/0
150 625
1.920E-02
5.760E-02
1.839E-01
250
175 729
1.646E-02
4.937E-02
1.576E-01
300
200 833
1.440E-02
4.320E-02
1.379E-01
350
250 1042
1.152E-02
3.456E-02
1.103E-01 400
300 1250
9.600E-03
2.880E-02
9.195E-02
2x250
350 1458
8.229E-03
2.469E-02
7.881E-02
2x300
400 1667
7.200E-03
2.160E-02
6.896E-02
2x350
500 2083
5.760E-03
1.728E-02
5.517E-02
2x500
Summary of Contents for Miyachi Unitek STA-100A
Page 1: ...990 351 Rev H AC WELDER STA SERIES OPERATION MANUAL...
Page 24: ......
Page 28: ......
Page 48: ......
Page 64: ......
Page 68: ...CHAPTER 5 MAINTENANCE STA SERIES AC CONTROLS 5 4 990 351...
Page 78: ......
Page 90: ......
Page 96: ...APPENDIX D SYSTEM TIMING STA SERIES AC CONTROLS D 2 990 351 Continuous Seam Weld...
Page 98: ...APPENDIX D SYSTEM TIMING STA SERIES AC CONTROLS D 4 990 351 Spot Welding...
Page 102: ......
Page 104: ......
Page 108: ......
Page 112: ......
Page 140: ......
Page 144: ......