background image

Alvarado Manufacturing Company, Inc. 

12660 Colony Street, Chino, CA 91710 

Phone: +1 (909) 591-8431 

Fax: +1 (909) 628-1403 

[email protected] 

www.alvaradomfg.com

PUD3448R2-1

SW1000/SW1000T 

Motorized Pedestrian Security Gate

Installation and Operation Instructions

Summary of Contents for SW1000

Page 1: ...ny Inc 12660 Colony Street Chino CA 91710 Phone 1 909 591 8431 Fax 1 909 628 1403 support alvaradomfg com www alvaradomfg com PUD3448R2 1 SW1000 SW1000T Motorized Pedestrian Security Gate Installation...

Page 2: ...sembly Installation 14 Primary Power Wiring 15 Access Control Wiring 16 Open Entry 17 Open Exit 17 Barrier Hold Open 18 Emergency Override 18 Emergency Override State Select 19 Breakaway Alarm Output...

Page 3: ...it is not installed and or operated correctly Therefore this manual must be read in its entirety and all safety and operations information must be followed Note the following precautions For indoor u...

Page 4: ...basis As owner or caretaker of the equipment it is essential that you maintain your SW1000s and ensure safe product use by the employees vendors and invitees that will be utilizing the product Refer...

Page 5: ...motor force Upon receipt of a dry contact input from an access control system or input device such as a push button the motorized barrier opens 90 degrees away from the signal direction The SW1000 is...

Page 6: ...Digital Position Encoder Motor Primary Power Terminal Block Access Control Terminal Block Optional Sensor Terminal Block Configuration Terminal Block Power Supply I O Motor Controller Board Communica...

Page 7: ...rminal block provides a connection point for the optional Exit Free Passage Sensor Configuration Terminal Block TB1 This terminal block is used for two purposes 1 to configure the emergency override s...

Page 8: ...e input signal is removed the gate resumes normal operation The SW1000 default configuration for fire alarm emergency override input signals is normally open but can be configured to interface with no...

Page 9: ...Make sure that none of these parts are missing and or damaged before beginning installation If parts are missing and or damaged please contact Alvarado Technical Support at 909 591 8431 Also Included...

Page 10: ...ollowing space requirements must be taken into consideration when determining the installation location Allocate 4 102mm of space between the back of the tower and adjacent wall or other surface Allow...

Page 11: ...ado suggests the use of surge protection on the high voltage power line to further protect electronics Drive Motor 24V BLDC Seal the floor area around the conduits running up and into the base plate T...

Page 12: ...installer s responsibility to ensure the following steps are completed before beginning the installation 1 All components and hardware have been unpacked correctly identified and moved to the installa...

Page 13: ...ll four 4 anchor holes to a depth of 3 64mm Figure 8 3 Using a shop vac vacuum any debris from the anchor holes Anchors will not tighten properly if debris is present 4 Insert anchors threaded side do...

Page 14: ...t four 4 anchor bolts and washers Figure 11 3 Using a torque wrench and 9 16 socket torque the anchor bolts to 20 ft lbs 4 Using a level verify the tower is plumb and level If necessary use shims to l...

Page 15: ...CAUTION The ground wire must be connected Serious injury may result if the ground wire is not properly connected Terminal 110V 220V Neutral White Blue Ground Green or Green Yellow Green Yellow Line Bl...

Page 16: ...g access control signals are provided on the following pages TB1 Configuration TB2 Optional Sensor TB3 Access Control TB9 Breakaway Output Terminal Description 1 3 Common Ground 4 N A 5 Emergency Over...

Page 17: ...15 Terminal Description 1 3 Common Ground 4 Entry Passage 5 Emergency Override 6 Exit Passage Terminal Description 1 3 Common Ground 4 Open Entry 5 Emergency Override 6 Open Exit Receipt of an input c...

Page 18: ...iption 1 3 Common Ground 4 Entry Passage 5 Emergency Override 6 Exit Passage Terminal Description 1 3 Common Ground 4 N A 5 Emergency Override State Select 6 Barrier Hold Open Receipt of an input sign...

Page 19: ...installed To configure normally closed install a wire jumper between TB1 5 and common ground as shown in Figure 18 This terminal is used to generate an output signal when the barrier is forced open b...

Page 20: ...ented such that the opening is aligned with the power button and fuse assembly and is seated properly in the base plate groove 2 Slide the upper cover over the tower assembly Figure 20 Rotate the uppe...

Page 21: ...ly using provided mounting screws Figure 22 Using a torque wrench and 1 4 Allen bit torque to 39 ft lbs 6 Align barrier with barrier clamps it is recommended to have a second person assist holding by...

Page 22: ...rrier is centered properly in the home position If the barrier home position needs to be reset refer to the SW1000 Configuration section beginning on Page 26 Powering On Off OPEN ENTRY TEST PROCEDURE...

Page 23: ...ection The barrier moves to the open position The barrier returns to the home position after 6 seconds TEST PROCEDURE GATE RESPONSE Push on the barrier until it breaks away The breakaway alarm sounds...

Page 24: ...ombined width does not exceed passage width prior to entering the gate Alvarado follows what we call the right hand rule Card readers are installed on the right hand side as the user enters the gate f...

Page 25: ...h it returns to the closed position 1 Place hands securely on the barrier and push until the barrier gives way The barrier moves freely An alarm sounds An output is generated 2 Promptly walk through t...

Page 26: ...No installation is required Simply copy SwingGateUtility exe over to the computer and double click to run 1 The RS232 programming cable is located at the base of the tower Figure 29 To access the cab...

Page 27: ...8431 Page 27 1 Double click SwingGateUtility exe to launch the utility This will bring up the SwingGate Utility main screen 2 Select COM port from the drop down menu and click Open Figure 30 Depending...

Page 28: ...a gate parameter enter a value in the text box and click Set For SW1000T tandem units settings must be configured on each side If after reading this document you are unclear regarding a particular se...

Page 29: ...the motor uses to keep the barrier closed during an attempt to force the barrier open When the force applied to the barrier exceeds this setting the barrier gives way and an alarm sounds The default s...

Page 30: ...nishes Powder coat finished surfaces may be cleaned using a soft damp cloth Any deep scratched in this type of finish should be touched up to prevent rust or corrosion from forming If left untreated r...

Page 31: ...so available to widen the passage area Alternate Finishes The post can be plated with an alternate plated finish such as bright chrome or brass Powder coating is also available Signage An Enter sign c...

Page 32: ...ments must be taken into consideration when determining the installation location Allocate 4 102mm of space between the back of the tower and adjacent wall or other surface Allow a minimum of 2 51mm o...

Page 33: ...Run primary power and access control conduit to the master gate Run DC power and communication conduit from the master gate to the slave gate Access Control Conduit Primary Power Conduit To Slave Gat...

Page 34: ...power is run from the master gate to the slave gate using the DC power crossover cable 10 1353 Follow the instructions below to connect DC power to the slave gate 1 Locate the DC power crossover cable...

Page 35: ...from the master gate to the slave gate using the communication crossover cable 10 1306 Follow the instructions below to connect communication to the slave gate 1 Locate the communication crossover cab...

Page 36: ...ers need to be removed Refer to the installation section of this manual for more information 1 Remove barrier clamps and tower covers to access the motor controller board 2 Locate the motor controller...

Page 37: ...SW1000 Installation and Operation Instructions PUD3448R2 1 For Assistance support alvaradomfg com 1 909 591 8431 Page 37 Appendix C Portable Baseplate Dimension 42 19 1071 5 52 48 1333 0 Figure C1...

Page 38: ...ate installation 1 Determine and mark the installation location 2 Place the baseplate in the marked location 3 Determine how the primary power and access control wiring will be routed to the master an...

Page 39: ...the tower assembly on the right hand side when viewed from the unsecured side If the gate was installed backwards the Open Entry and Open Exit access control wires will need to be reversed to correct...

Page 40: ...hor Description 1 2 1 27 15 A Flores Added Appendix Setting the Home Position 2 0 10 5 15 A Flores Includes 2015 design changes Added configuration operation and maintenance instructions Updated docum...

Page 41: ...SW1000 Installation and Operation Instructions PUD3448R2 1 For Assistance support alvaradomfg com 1 909 591 8431 Page 41 This page intentionally left blank...

Page 42: ...2014 Alvarado Manufacturing Company Inc This work may not be reproduced published or redistributed in whole or in part without the express prior written permission of Alvarado...

Reviews:

Related manuals for SW1000