8.6.5
High Compressor Last Run Time Alarm –
Occurs when the compressor takes longer to pressurize the air tank than the
set point for the alarm.
See section 13.17 for troubleshooting information.
8.6.6
Compressor Total Hour Alarm –
Occurs when the compressor has reached a recommended maintenance
interval. Perform the required maintenance.
See section 10.3 for maintenance information.
8.6.7
High Duty Cycle Alarm –
Occurs when the duty cycle rises above the alarm set point. The duty cycle is
calculated based on the previous two compressor last run time values.
See section 13.11 for troubleshooting information.
8.7 Adjusting & Resetting Dryer Set Points
Dryer Set Points are simply limits programmed for a specific reading. Once this limit
is reached (or exceeded) this results in an alarm for that reading. Each of these set
points is factory programmed with a default value based on typical usage of the air
Dryer. Many of the set points for Dryer alarms can be modified to levels more
closely based upon your specific application.