Altec AIR, LLC
P210WLP Series Air Dryer User’s Guide
Page 32 of 96
P017455 – Rev. N
HUMIDITY
– Humidity level of the system.
8.5.5.2
Compressor Run Time
LAST
– How many minutes the compressor ran during the last Air Tank
pressurization cycle.
TOTAL
– Number of hours of compressor run time since the total run
time value was manually reset
8.5.5.3
System Status
SYS STATUS
– Signal to determine if the unit is online or in shutdown
- Running Status of the system:
ONLINE
– System is online.
SHUTDOWN
– System has been shutdown as a result of either a
humidity or high cabinet temperature alarm.
CAB TEMP –
Temperature of the dryer cabinet compartment
DUTY CYCLE
– Compressor run time as a percentage of total cycle time
8.6 Identifying Dryer Alarms
8.6.1
High Outlet Pressure Alarm -
Occurs when the Outlet Pressure (
OUTLET
) rises above the alarm set point
for more than one (1) minute.