P50 Agile P15D
14 Technical Specifications
P15D/EN TM/B
14-5
III.
VA burden of Status S4 (Remote Trip)
For 100 to 230 V AC nominal voltage range < 12 VA
For 100 to 230 V DC nominal voltage range < 4 W
For 24 V to 50 V DC nominal voltage range < 4 W
Note: P15D is not supplied from auxiliary supply and current is below the
minimum current required to power ON the relay. Relay draws power
from Remote Trip input to power ON and provide tripping output to CB
IV.
Operating voltage range
90% of lower nominal range and 120% of upper nominal range for DC
90% of lower nominal range and 110% of upper nominal range for AC
V.
Pick up voltage range
For 100 to 230 V aux. supply : 60 – 80V
For 24 to 50 V aux. supply : 15 – 19V
VI.
Drop off voltage range
For 100 to 230 V aux. supply : 30 – 60V
For 24 to 50 V aux. supply : 7 – 15V
VII.
Filtering Time
< 40 ms for S1 ,S2,S3
VIII.
Logic input recognition time
For S1,S2,S3 : filtering time + 5ms ± 5 ms
For S4 (Remote Trip) : 3.5 sec ± 5%
Output Contact
I.
Latching contact
(Signalling Contact )
Making capacity
Making capacity – 2A /250 V AC
Breaking capacity
Breaking capacity - 60 W / 62.5 VA
II.
Non Latching contact
Continuous
Continuous 5A/250 V AC
Make & carry
30A for 3sec AC/DC
Short time withstand capacity
50A for 1sec AC/DC
Breaking capacity
AC- 1250 VA max. 5A or 300 V (PF=
0.4)
DC- 100 W resistive max. 5A or 300 V
-50 W Inductive (L/R =45 ms) max.
5A or 300 V
Operating Time
<10 msec
Minimum no. of operations
10,000 operation loaded condition &
unloaded 100,000 operations
III.
Impulse Output for tripping coil
Impulse output for the tripping
coil
12 V - 24 VDC (Energy <= 0.1 J)
Note: The trip energy for the trip coil is stored by a capacitor built into the protection relay. The capacitor is charged by a current
input or the auxiliary voltage. The duration of the trip pulse is 50 ms (if output is not burden). The pause between the individual pulses
depends on the impedance of the trip coil and on the current level. The pulse lasts as long as the activation threshold is exceeded. The
voltage level of the energy output depends on the discharging time
IV.
Impulse Output for Flag Indicator or Auxiliary Relay Impulse
output
for
Flag
Indicator or auxiliary Relay
12 V - 24 VDC (Energy <= 0.03 J)
Note: The trip energy for the flag indicator is stored by a capacitor built into the protection relay. The capacitor is charged by a current input or the
auxiliary voltage. The duration of the trip pulse is 50 ms (if output is not burden). The pause between the individual pulses depends on the
impedance of the flag indicator and on the current level. The pulse lasts as long as the activation threshold is exceeded The impulse output for flag
indicator and trip coil drive energy from same source. The flag out use additional capacitor to store required energy. If more energy is take from
flag output than specified, then it will affect energy output of trip coil
Accuracy of protection function
Overcurrent & Earth Fault function
I.
For operating Value
Pick-up
S10% / - 5%
Minimum Trip Level of IDMT
1.05 x Settings ± 5%
Drop –off
0.95 x Setting ± 5% for settings >=20%
0.90 x Setting ± 10% for settings < 20%
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......