7 Protection Parametre Settings
P50 Agile P15D
7-12
P15D/EN TM/B
2.8.10
Cold Load Pickup
Sr. No
Parameter
Default setting
Setting Range
1.
tcold Time Delay
7200
00000 to 14400s step 1s
This setting determines the time the load needs to be de-energized (dead time) before the new settings are applied.
2.
tclp Time Delay
7200
00000 to 14400s step 1s
This setting controls the period of time for which the relevant overcurrent and earth fault settings are altered or inhibited following circuit
breaker closure.
3.
I>1 Status
Enabled
Block / Enabled
The I>1 status cells have two setting options, "Enable" and "Block". Selecting "Enable" for a particular stage means that the current and
time settings programmed in the following cells will be those that are adopted during the "tclp" time. Selecting "Block" simply blocks the
relevant protection stage during the "tclp" time. It also removes the following current and time settings for that stage from the menu.
4.
I>1 Current Set
1.5*In
0.20 to 4.00*In step 0.01*In
This setting determines the new pick-up setting for first stage overcurrent element during the tclp time delay.
5.
I>1 Time Delay
0.01
000.00 to 100.00s step 0.01s
This setting determines the new operating time delay for the first stage definite time overcurrent element during the tclp time.
6.
I>1 TMS
0.1
0.025 to 1.200 in step 0.005
This setting determines the new time multiplier setting for the first stage element to adjust the operating time of the IEC IDMT
characteristic during the tclp time.
7.
I>2 Status
Enabled
Block / Enabled
The I>2 status cells have two setting options, "Enable" and "Block". Selecting "Enable" for a particular stage means that the current and
time settings programmed in the following cells will be those that are adopted during the "tclp" time. Selecting "Block" simply blocks the
relevant protection stage during the "tclp" time. It also removes the following current and time settings for that stage from the menu.
8.
I>2 Current Set
1.5*In
0.20 to 4.00*In step 0.01*In
This setting determines the new pick-up setting for second stage overcurrent element during the tclp time delay.
9.
I>2 Time Delay
0.01
000.00 to 100.00s in step 0.01s
This setting determines the new operating time delay for the second stage definite time overcurrent element during the tclp time.
10.
I>2 TMS
0.1
0.025 to 1.200 in step 0.005
This setting determines the new time multiplier setting for the second stage element to adjust the operating time of the IEC IDMT
characteristic during the tclp time.
11.
I>3 Status
Enabled
Block / Enabled
The I>3 status cells have two setting options, "Enabled" and "Block". Selecting "Enable" for a particular stage means that the current
and time settings programmed in the following cells will be those that are adopted during the "tclp" time. Selecting "Block" simply blocks
the relevant protection stage during the "tclp" time. It also removes the following current and time settings for that stage from the menu
12.
I>3 Current Set
1.5*In
0.20 to 4.00*In step 0.01*In
This setting determines the new pick-up setting for third stage overcurrent element during the tclp time delay.
13.
I>3 Time Delay
0.01
000.00 to 100.00s step 0.01s
This setting determines the new operating time delay for the third stage definite time overcurrent element during the tclp time.
14.
I>3 TMS
0.1
0.025 to 1.200 in step 0.005
This setting determines the new time multiplier setting for the third stage element to adjust the operating time of the IEC IDMT
characteristic during the tclp time.
15.
IN>1 Status
Enabled
Block / Enabled
The IN>1 status cells have two setting options, "Enabled" and "Block". Selecting "Enable" for a particular stage means that the current
and time settings programmed in the following cells will be those that are adopted during the "tclp" time. Selecting "Block" simply blocks
the relevant protection stage during the "tclp" time. It also removes the following current and time settings for that stage from the menu.
16.
IN>1 Current Set
0.2*In
0.20 to 4.00 step 0.01*In
This setting determines the new pick-up setting for first stage earth fault element during the tclp time delay.
17.
IN>1 Time Delay
0.01
000.00 to
200s step 0.01s
This setting determines the new operating time delay for the first stage definite time element during the tclp time.
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......