![Alstom MiCOM P50 Agile P15D Technical Manual Download Page 136](http://html1.mh-extra.com/html/alstom/micom-p50-agile-p15d/micom-p50-agile-p15d_technical-manual_2908934136.webp)
6 Protection Functions
P50 Agile P15D
6-6
P15D/EN TM/B
timer to zero, the overcurrent timer for that stage will reset instantaneously as soon as the current falls
below a specified percentage of the current setting (typically 95%).
Another possible situation where the timer hold facility may be used to reduce fault clearance times is
for intermittent faults. An example of this may occur in a plastic insulated cable. In this application it is
possible for the fault energy to melt and reseal the cable insulation, thereby extinguishing the fault.
This process repeats to give a succession of fault current pulses, each of increasing duration with
reducing intervals between the pulses, until the fault becomes permanent.
When the reset time is instantaneous, the device will repeatedly reset and not be able to trip until the
fault becomes permanent. By using the Timer Hold facility the device will integrate the fault current
pulses, thereby reducing fault clearance time.
The timer hold facility is available to all three stages of OC and EF functions.
The Definite Time Reset characteristic is applicable for IEC curves / DT.
The value of the Reset Timer depends on the type of the timer associated to the pick-up phase (Earth)
threshold.
Type of timer associated with phase (earth)
threshold
Reset Timer
Self-Powered
- For DT time delay
DT
- For IDMT time delay
DT
Aux. Powered
-
For DT time delay
DT
-
For IDMT time delay
DT
The range of DT time setting is 0 – 100 sec in steps of 0.01 sec.
Note:
For aux. powered P15D relay, if load current reduces below minimum value required to keep relay
energised, then the HOLD/RESET timer will reset to zero.
2.2
Thermal Overload Function
The heat generated within an item of plant, such as a cable or a transformer, is the resistive loss
(I
2
Rt). The thermal time characteristic is therefore based on the square of the current integrated over
time. The device automatically uses the largest phase current for input to the thermal model.
The equipment is designed to operate continuously at a temperature corresponding to its full load
rating, where the heat generated is balanced with heat dissipated. Over-temperature conditions occur
when currents in excess of their maximum rating are allowed to flow for a period of time. It is known
that temperature changes during heating follow exponential time constants.
The device provides single time constant characteristic which is used to protect cables, dry type
transformers (e.g. type AN), and capacitor banks.
Thermal overload protection is designed to prevent the electrical equipment when operating
temperature is exceeded the maximum designed temperature. The fundamental currents are
measured and analysed to monitor the thermal state. In case of thermal overload function the
calculation of the Time to Trip is given by:
t =
τ
ln ((K²- A)/ (K²- Th. Trip))
Where:
t:
Time to trip (in seconds)
τ
:
Thermal time constant (Te, in seconds) of the equipment to be protected
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......