7 Protection Parametre Settings
P50 Agile P15D
7-6
P15D/EN TM/B
Sr. No
Parameter
Default setting
Setting Range
20.
SET Year
***
00 to 99 years step 1
The Year setting is needed when the relay is not connected to SCADA system.
Note :*** The relay displays the current Date/Time set in the relay
2.4
Configuration settings
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to 9999
This setting is used to enter a new password.
2.
Restore Defaults
No Operation
No Operation / All Settings / Setting Group 1
/ Setting Group 2
This setting is used to restore a setting group to factory default settings.
To restore the default values to the settings in any Group settings, set the ‘restore defaults’ cell to the relevant Group number.
Alternatively it is possible to set the ‘restore defaults’ cell to ‘all settings’ to restore the default values to all of the IED’s settings, not just
the Group settings.
While editing the relay settings through UI, the new updated value is kept in a temporary memory. After editing all settings in a
respective function, there is an option to save setting by pressing SET key or cancel changes by selecting RESET key. If SET key is
pressed, relay saves the setting from temporary memory to actual setting file. If RESET key is pressed, relay discards the temporary
memory.
Note:
If the key pad is left untouched for 100 sec, any changes made are aborted and the
relay returns to the Main Menu.
Restoring defaults to all settings includes the rear communication port settings,
which may result in communication via the rear port being disrupted if the new
(default) settings do not match those of the master station.
3.
Active Settings
Group 1
Group 1 / Group 2
This setting determines the active setting group.
4.
Setting Group 1
Enabled
Enabled
This setting is used to Enable / Disable Settings Group 1. If the setting group is disabled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
5.
Setting Group 2
Disabled
Enabled / Disabled
This setting is used to Enabled / Disable the active group 2 setting. If the setting group is disabled from the configuration, then all
associated settings and signals are hidden, with the exception of this setting.
6.
System Configuration
Disabled
Enabled / Disabled
This setting is used to set the System Configuration menu, visible further on in the relay settings menu. The 2nd Harmonic blocking
related parameters are present inside.
7.
Overcurrent
Enabled
Enabled / Disabled
This setting is used to enable or disable the Phase Overcurrent Protection function. If it is disabled then all associated settings and
signals are hidden, with the exception of this setting.
8.
Earth Fault
Enabled
Enabled / Disabled
This setting is used to enable or disable the Earth Fault Protection function.
9.
Thermal Overload
Disabled
Enabled / Disabled
This setting is used to enable or disable the Thermal Overload function.
10.
Cold Load Pickup
Disabled
Enabled / Disabled
This setting is used to enable or disable the Cold Load Pickup function.
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......