P50 Agile P15D
13 Installation
P15D/EN TM/B
13-15
2.
Binary inputs terminal details are as under :-
Binary Inputs
Terminal
S1
A15
A17
S2
A12
A14
S3
A11
A13
Remote Trip (S4)
A16
A18
3.
Observed binary input (S1,S2,S3) status in system data menu on LCD display
4.
For Testing Remote trip input, apply rated voltage at A16 and A18 terminal. Relay will
immediately go in to tripping mode.
2.2.7
Testing for optional auxiliary power supply
The P15D is a dual power relay and can function with or without an external Auxiliary power supply.
To test this function apply rated auxiliary supply at relay terminal A (19 & 20) with proper polarity and
complete function of the relay can be tested.
It is suggested to use Numerical test kit while testing relay P15D. For timing measurements use the
optional auxiliary supply to power ON the relay.
2.2.8
Testing for trip coil
The Impulse output for Circuit Breaker Tripping coil with trip energy (12 to 24 VDC, <= 0.1 J) is
provided by a capacitor in the protection relay. The length of the pulse is 50 ms (if output is not
burdened).The pause between the individual pulses depends upon the impedance of trip coil (C.B.)
and the current level. Pulses are continued until the CB operates and fault current becomes zero.
Testing can be performed at trip coil terminal - A1 (-ve) & A3 (+ve).The trip coil output function can be
also operated by using TEST key on the relay front panel.
2.2.9
Testing for flag coil
The Impulse output for external Flag indicator with a trip energy of (12 to 24 VDC, <= 0.03 J) is
provided by a capacitor in the protection relay. The length of the pulse is 50 ms (if output is not
burdened).The pause between the individual pulses depends upon the impedance of flag indicator
and on the current level. Testing can be performed at Flag coil terminal – A2 (-ve) & A4 (+ve).
2.2.10
Functional test
2.2.10.1
Testing of Overcurrent Protection
1.
Overcurrent I>1 function
: Pickup test
I>1 Setting
R Phase
Y Phase
B Phase
Limit value (amp)
1A
5A
1A
5A
1A
5A
1A
5A
Min
Max
Min
Max
100%
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......