![Alstom MiCOM P50 Agile P15D Technical Manual Download Page 134](http://html1.mh-extra.com/html/alstom/micom-p50-agile-p15d/micom-p50-agile-p15d_technical-manual_2908934134.webp)
6 Protection Functions
P50 Agile P15D
6-4
P15D/EN TM/B
2
PROTECTION FUNCTIONS
2.1
Overcurrent / Earth Fault function
Most power system faults result in an overcurrent of some kind. It is the job of protection devices,
formerly known as relays but now known as Intelligent Electronic Devices (IEDs), to protect the power
system from such faults. The general principle is to isolate the faults as quickly as possible to limit the
danger and prevent unwanted fault currents flowing through systems, which can cause severe
damage to equipment and systems. At the same time, we wish to switch off only the parts of the grid
that are absolutely necessary, to prevent unnecessary blackouts. The protection devices that control
the tripping of the grid's circuit breakers are highly sophisticated electronic units, providing an array of
functionality to cover the different fault scenarios for a multitude of applications.
The described products offer a range of overcurrent protection functions including:
•
Phase Overcurrent protection
•
Earth Fault Overcurrent protection
To ensure that only the necessary circuit breakers are tripped and that these are tripped with the
smallest possible delay, the IEDs in the protection scheme need to co-ordinate with each other.
Various methods are available to achieve correct co-ordination between IEDs in a system.
These are:
•
By means of time alone
•
By means of current alone
•
By means of a combination of both time and current.
Grading by means of current is only possible where there is an appreciable difference in fault level
between the two locations where the devices are situated. Grading by time is used by some utilities
but can often lead to excessive fault clearance times at or near source substations where the fault
level is highest. For these reasons the most commonly applied characteristic in co-ordinating
overcurrent devices is the IDMT (Inverse Definite Minimum Time) type.
The relay is designed for three stages programmable OC and EF functions. All three stages of
overcurrent and earth fault protection function are programmable as Inverse Definite Minimum Time
(IDMT) or Definite Time (DT) delay.
2.1.1
IDMT Characteristics
All three stages of OC and EF functions are programmable as per IDMT characteristic based on IEC
and IEEE standards. The inverse time delay is calculated with the following mathematical formula:
k
t=T*
I
1
Is
L
a
+
−
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......