P50 Agile P15D
7 Protection Parametre Settings
P15D/EN TM/B
7-7
Sr. No
Parameter
Defaults setting
Setting / Ranges
11.
Measure’t Setup
ABC
ABC /RYB
This setting determines the representation of Phases. Based on this setting, the representation in measurements, records by the IED
etc. will change. No change is expected for the stored records, if any.
12.
Under Current Protection
Disabled
Enabled / Disabled
This setting is used to enable or disable the Under Current Protection.
13.
Under Current Protection
Disabled
Enabled / Disabled
This setting is used to enable or disable the Under Current Protection.
14.
Setting Value
Secondary
Not editable
This setting determines the reference for all settings dependent on the transformer ratios; referenced to the secondary.
2.5
CT and VT Ratio settings
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to 9999
This setting is used to enter a new password.
2.
Phase CT Primary
00100
00001 to 30000A in step 1A
This setting determines to sets the Phase Current Transformer input primary current rating.
3.
E/F CT Primary
00100
00001 to 30000A in step 1A
This setting determines to sets the Earth Current Transformer input primary current rating.
2.6
Record Control settings
Sr. No
Parameter
Default setting
Setting Range
1.
Password
0000
0000 to 9999
This setting is used to enter a new password
2.
Clear Events
No
Yes / No
Selecting “Yes” will erase the existing Events Stored from the relay.
3.
Clear Faults
No
Yes / No
Selecting “Yes” will erase the existing Fault Records from the relay.
4.
Clear Dist Recs
No
Yes / No
Selecting “Yes” will erase the existing Disturbance Records from the relay.
5.
Clear Maint
No
Yes / No
Selecting “Yes” will erase the existing Maintenance Records from the relay.
6.
Thermal Reset
No
Yes / No
Selecting “Yes” will reset the existing Thermal State to zero.
2.7
Communication settings
Sr. No
Parameter
Default setting
Setting Range
1.
Password
0000
0000 to 9999
This setting is used to enter a new password.
2.
RP1 Address
001
001 to 247 step 1
This setting is used to set the unique address for the relay, so that only one relay is accessed by the master station software.
3.
RP1 Baud rate
57600
9600 / 14400 / 19200 / 28800 / 38400 /
57600
This setting controls the communication speed between relay and master station. It is important that both relay and master station are
set at the same speed setting.
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......