P50 Agile P15D
7 Protection Parametre Settings
P15D/EN TM/B
7-11
2.8.7
IN>3 Function
Sr. No
Parameter
Default setting
Setting Range
1.
IN>3 Function
IEC S Inverse
Disabled / DT / IEC S Inverse / S Inverse 1.3Sec / IEC V
Inverse / IEC E Inverse / UK LT Inverse / IEEE M Inverse / IEEE
V Inverse / IEEE E Inverse / US Inverse / US ST Inverse
This setting determines the tripping characteristic for the third stage earth fault current element.
2.
IN>3 Current Set
1*In
If DT 1.0 to 35.00* In step 0.01*In
If IDMT then 0.10 to 2.50* In step 0.01*In
This setting determines the pick-up setting for third stage earth fault current element.
3.
IN>3 Time Delay
1
000.00 to 200.00s step 0.01s
This setting determines the time-delay for the definite time setting, if selected for third stage earth fault element.
4.
IN>3 TMS
1
0.025 to 1.200 step 0.005
This setting determines the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.
5.
IN>3Time Dial
1
000.01 to 100.00 step 0.01
This setting determines the time multiplier setting to adjust the operating time of the IEEE IDMT curves.
6.
IN>3 tRESET
0
000.00 to 100.00s step 0.01s
This setting determines the reset/release time for all types of curves.
7.
IN>3 2H Blocking
Disabled
Enabled / Disabled
This setting determines the enabling/disabling of blocking third stage of Earth fault element due to presence of inrush current.
If IN>3 Blocking and 2nd Harmonic both setting are enabled, then (IN>3) trip command will be blocked in case 2nd harmonics content
in any phase is above the 2ndHarm Thresh. and fundamental current is below I> lift 2H setting . (Set in SYSTEM CONFIG Menu.)
2.8.8
Thermal Overload
Sr. No
Parameter
Default setting
Setting Range
1.
Characteristic
Single
Disabled/ Single
This setting determines the operating characteristic of the thermal overload element.
2.
Thermal Trip
1*In
0.10 to 4.00* In step 0.01 In
This setting determines the maximum full load current allowed and the pick-up threshold of the thermal characteristic.
3.
Thermal Alarm
70
50 to 100% step 1%
This setting determines the thermal state threshold corresponding to a percentage of the trip threshold at which an alarm will be
generated.
4.
Time constant 1
10
001 to 200 min step 1min
This setting determines the thermal time constant for a single time constant characteristic.
5.
K factor
1.05
1 to 1.5 step 0.01
This setting specify the k constant of thermal over load function
2.8.9
Undercurrent
Sr. No
Parameter
Default setting
Setting Range
1.
I< Status
Disabled
Enabled / Disabled
This setting is used to enable or disable the Undercurrent protection.
2.
I<
1*In
0.1In – 1.00*In step 0.01*In
This setting determines Pick-up setting for undercurrent element.
3.
tI<
10
0.20s to 100s in step 0.01s
This setting determines the time-delay for tripping.
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......