8 Monitoring & Control
P50 Agile P15D
8-4
P15D/EN TM/B
2
MONITORING & CONTROL
2.1
Monitoring Functions (Event, Fault, Disturbance Record)
The IED logs three different types of record. These are Event, Fault and Disturbance records, which
are stored in the IEDs non-volatile memory. It is important to log records because this allows you to
establish the sequence of events that occurred, for example following a particular power system
condition.
The device is capable of storing up to:
•
100 event records
•
5 Fault records
•
5 Disturbance records
When the available space is exhausted, the oldest record is automatically overwritten by the new one.
The IEDs internal clock provides a time tag for each event, to a resolution of 1 ms.
The VIEW RECORDS column contains details of these Event and Fault records, which can be
displayed on the IEDs front panel, although it is easier to view them using the settings application
software.
The device supports IEC 60870-5-103 and Modbus protocol. It auto-detects IEC-60870-5-103 and
MODBUS command and responds in respective language. There is no any specific setting which
defines the protocol.
Note:
The MODBUS by design does not support event functionality.
2.1.1
Event Records
Event records are generated when certain events happen. A change in any digital input signal or
protection element output signal causes an event record to be created. These events are generated
by the protection software and immediately time stamped. They are then transferred to non-volatile
memory for storage.
The device continuously monitors logical and physical status. There are three physical Binary inputs
provided, marked as S1, S2 and S3. The S1 is designed to monitor breaker status and also use this
status for Cold load operation, while S2 and S3 are general purpose. Any physical or logical change is
recorded as event. These events are stored in internal, non-volatile memory along with a time stamp.
Some of the events recorded include: Protection pickup, Relay Reset and CB Trip. A complete list can
be found in protocol document. Up to 100 such events can be stored and downloaded for detailed
analysis. Details of event data are as follows:
Capacity: 100 events
Time-tag: 1 millisecond
Triggers: Any selected protection alarm and threshold, Logic input change of state, Self-test
events and setting changes.
The user can view the event records either using the front panel interface, the USB port or remotely
using the rear EIA(RS)485 port.
Summary of Contents for MiCOM P50 Agile P15D
Page 2: ......
Page 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Page 9: ...SAFETY INFORMATION CHAPTER 2...
Page 10: ...Safety Information Pxxx 2...
Page 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Page 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Page 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Page 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Page 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Page 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Page 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Page 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Page 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Page 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Page 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Page 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Page 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Page 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Page 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Page 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Page 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Page 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Page 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Page 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Page 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Page 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Page 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Page 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Page 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Page 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Page 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Page 223: ......