Fault: When the following bits show a 1,
the following faults are displayed.
Table M
— Event Codes
Code
Mode
Code
Mode
Code
Mode
000
Standby
003
Boost 1
006
Inverter
001
Line
004
Buck 1
009
Shutdown
002
Boost 2
005
Buck 2
010
Bypass
2.
If less than 200 events occurred, the last entry will appear as:
eventX=00/00/00 00:00:00 0000000000000000, 0000000000000000, 000
3.
To clear the log, type
eventclr
and press
Enter
. It takes the Alpha FXM 30 seconds to clear the log. Do
not enter any other commands during this time.
4.
To see a specific event, type
eventX
where X is from 1 to 200 and press
Enter
. To see a range of events
(for example, events 20 to 30), type
eventX-X
where X are events from 1 to 200 and press
Enter
. To
clear the log, type
eventclr
and press
Enter
. It takes the Alpha FXM 30 seconds to clear the log. Do not
enter any other commands during this time.
5.
To see a specific event, type
eventX
where X is from 1 to 200 and press
Enter
. To see a range of events
(for example, events 20 to 30), type
eventX-X
where X are events from 1 to 200 and press
Enter
.
7.5.9
This command resets all parameters that are user-configurable. All previously programmed operation will
be lost. Implement a backup plan for mission critical operations. This command is password protected.
Page
87
to
106
Restoring All Parameters to Default Values
The purpose of this command is to reset the Alpha FXM to the factory default state.
See Table D for a list
of parameters that will be restored to their default values.
CAUTION!