Table B
— Control Menu
LCD display
Meaning
Description
QUAL TIME
Line qualify
time
Let
’s you set how long it takes for the Alpha FXM to return to Line
mode after the line has become requalified to make sure the line is
stable. It can be set to 3, 10, 20, 30, 40 or 50 seconds. The factory
default setting is 3 seconds. Also See #34: Line Qualify Time in Table
I.
BATT COMP
Battery
temperature
compensation
Let
’s you set the battery temperature compensation to match the
batteries you are using. It can be set to -2.5, -4, -5 or -6 mV/°C/Cell.
The factory default setting is -5 mV/°C/Cell.
DATE FRMT
Date Format
Selection
This lets you toggle the Alpha FXM date format between YY-MM-DD,
MM-DD-YY, YYY-MM-DD, MM-DD-YYYY, DD-MM-YYYY, YY-TXT-
DD, TXT-DD-YY, DD-TXT-YY, YYYY-TXT-DD, TXT-DD-YYYY, DD-
TXT-YYYY, YYYY-DD-TXT, YY-DD-TXT, YYYY-DD-MM, YY-DD-
MM. The factory default setting is MM-DD-YY.
CLOCK FRMT
Clock display
format option
Let’s you select which format to display time information: in 24 hour
clock format or 12 hour clock (AM/PM) format.
INV RECORD
Inverter
record clear
This clears the inverter counter and timer from the LCD system
status menu. This does not clear the 200-event log.
CHGR CUR
Charger
current
Allows you to set the battery charger current to either 0 A, 1 A, 2 A, 3
A or 4 A for 48V systems and 5A or 6A for 24V systems. NOTE:
Setting the battery charger to 0wAill turn the charger off.
RELAY TEMP
Relay
temperature
Temperature setting to activate the specified dry contact. The
configured dry contact will activate when the set battery temperature
is reached. Setting range: 20ºC to 55ºC (68 ºF to 131ºF). The default
setting is 55ºC (68 ºF). The relay is de-energized when the
temperature drops by 10ºC (18ºF).
TEMP DISP
Temperature
display format
The temperature can be displayed in Celsius or Fahrenheit.
DAYLIGHT
Daylight
saving option
Switch ON this option to activate Day Light Saving time.
CONFIGURE IP
IP
Let’s you configure the UPS IP address