Enter the Battery
voltage and
nominal load
}
From the data sheet of
the batteries enter the
2 closest currents and
discharge hours
Enter the
number of
parallel strings
4.
The Peukert’s capacity for the series combination (Batteries #1 and #2) is 120.55 Ah.
5.
The Peukert’s capacity for the parallel combination (Batteries #1, #2 and #3, #4) is:
2 x 120.55 Ah = 241.10 Ah.
A.5 Using the Spreadsheet
Download the
spreadsheet “Peukert’s Parameters Calculator.xls” from www.alpha.ca website.
CAUTION!
The battery runtime is only an estimation and must not be relied on for critical applications. The battery
runtime remaining is applicable only in inverter/backup mode.