Table T
— Boost/Buck/Line Transfer Thresholds
Parameter
Value
120 Vac Units
230 Vac Units
High Line Transfer
High Line Retransfer
152 Vac
146 Vac
282 Vac
272 Vac
Buck 1 Transfer
Buck 1 Retransfer
134 Vac
128 Vac
250 Vac
236 Vac
Boost 1 Retransfer
Boost 1 Transfer
116 Vac
112 Vac
210 Vac
207 Vac
Boost 2 Retransfer
Boost 2 Transfer
102 Vac
98 Vac
180 Vac
176 Vac
Low Line Retransfer
Low Line Transfer
97 Vac
88 Vac
162 Vac
151 Vac
Table U
— Regulatory
Parameter
Value
Electrical Safety
UL 1778, CSA 107.3, EN 62040-1-2, EN60950-1.
Emission
FCC Part 15, Subpart B, Class A, CSPR22, EN55022 Level A.
Marks
C
CSA
US
, CE (230 Vac versions only).
Packaging
Designed to meet requirements for ISTA program.