Chapter 4: Installing the Switches on a Table or in an Equipment Rack
76
Wiring the DC Connectors on the AT-x510-28GSX-80 Switch
The procedures in this section are for the AT-x510-28GSX-80 Switch
which has DC power supplies. They explain how to connect the grounding
and power wires to the DC connectors on the back panel of the switch. If
you do not have a DC powered switch, go to Chapter 5, “Verifying the
Status of VCStack” on page 85.
Note
Do not power on the switch after completing these procedures,
Instead, go to Chapter 5, “Verifying the Status of VCStack” on page
85.
Warning
This equipment must be installed in a Restricted Access location.
E45
Required
Material and
Tools
The procedure requires the following material:
One 12 AWG stranded grounding wire. The standard color for the
wire is green with a yellow stripe.
One 16 AWG minimum stranded power wire for the -48/-60VDC
connection. The standard color for the wire is red.
One 16 AWG minimum stranded power wire for the RETURN
connection. The standard color for the wire is black.
One ring lug suitable for a M4/#8 stud and 12 AWG wire. An
example of a ring lug is shown in Figure 28.
Figure 28. Ring Lug
Note
The grounding and power wires should be stranded wires. Do not
use solid wires.
Summary of Contents for AT-x510-28GPX
Page 10: ...Tables 10 ...
Page 14: ...Preface 14 ...
Page 48: ...Chapter 1 Overview 48 ...
Page 70: ...Chapter 3 Beginning the Installation 70 ...
Page 84: ...Chapter 4 Installing the Switches on a Table or in an Equipment Rack 84 ...
Page 128: ...Chapter 9 Troubleshooting 128 ...