To Connect Electrical Service To The
Tumble Dryer
NOTE: The wiring diagram is located in the junction
box.
1. Install a circuit breaker as close to the tumble dryer as possi-
ble. If more than one tumble dryer is being installed, a discon-
nect switch or circuit breaker should be provided for each.
This will make it possible to disconnect each tumble dryer for
maintenance purposes.
2. Connect the wire leads to the appropriate labeled terminal on
the terminal block. The ground wire must be connected to the
ground connection as shown in
Service/Ground Location
.
Electrical Specifications
NOTE: Wire sizes were obtained from the Canadian
Electrical Code for 75 C. wire and are intended for use
as a guideline only. Electrical connections should be
made by a qualified electrical contractor in accordance
with all applicable local and national requirements.
NOTE: Electrical specifications below are subject to
change without notice. Always refer to product serial
plate for most current specifications of product being
installed.
CAUTION
Use copper conductors only with the following rating
when wiring appliance to electric supply: Dryer gas
and steam heat models require 187°F (75°C) mini-
mum. Dryer electric heat models require 194°F (90°C)
minimum.
W936
NOTE: Connect this appliance to an individual branch
circuit.
NOTE: 3 Phase Only – Each tumble dryer must be con-
nected to its own individual branch circuit breaker, not
fuses, to avoid the possibility of “single phasing” and
causing premature failure of the motor(s).
120 Series Gas and Steam Models
Code
Voltage
Cycle
Phase
Terminal
Block Con-
nections Re-
quired
Full Load
Amps
Recommend-
ed Circuit
Breaker Rat-
ing Amps
Wire Size
AWG [mm2]
Q
200-240
50-60
3
L1, L2, L3
and ground
7
15
14 [2.5]
N
440-480
50-60
3
L1, L2, L3
and ground
4
15
14 [2.5]
P
380-415
50-60
3
L1, L2, L3
and ground
4
15
14 [2.5]
Table 7
Electrical Requirements
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
53
Part No. 70532501ENR7